Rated capacity (KVA) | Vector Group | Voltage Combination | | | No-load loss | Load loss | No-load current | lmpedance | ||
| | HV | Tapping range | LV | | | | | ||
30 | Yyn0 / Dyn11 | 10 6.3 6 | ±5% ±2X2.5% (+3/-1)X2.5% | 0.4 | 135 | 640 | 2 | 4.0 | ||
50 | | | | | 195 | 900 | 2 | | ||
80 | | | | | 265 | 1240 | 1.5 | | ||
100 | | | | | 290 | 1410 | 1.5 | | ||
125 | | | | | 340 | 1660 | 1.3 | | ||
160 | | | | | 385 | 1910 | 1.3 | | ||
200 | | | | | 445 | 2270 | 1.1 | | ||
250 | | | | | 515 | 2480 | 1.1 | | ||
315 | | | | | 635 | 3120 | 1 | | ||
400 | | | | | 705 | 3590 | 1 | | ||
500 | | | | | 835 | 4390 | 1 | | ||
630 | | | | | 965 | 5290 | 0.85 | | ||
630 | | | | | 935 | 5360 | 0.85 | 6.0 | ||
800 | | | | | 1090 | 6260 | 0.85 | | ||
1000 | | | | | 1270 | 7310 | 0.85 | | ||
1250 | | | | | 1500 | 8720 | 0.85 | | ||
1600 | | | | | 1760 | 10500 | 0.85 | | ||
2000 | | | | | 2190 | 13000 | 0.7 | | ||
2500 | | | | | 2590 | 15400 | 0.7 | |
Electrical Isolation: Complete isolation between primary and secondary circuits to prevent electrical noise, surges, and harmonics.
Epoxy Resin Insulation: Superior moisture resistance, high dielectric strength, and durability for long-term operation.
Low Noise Operation: Noise level ≤ 50 dB, suitable for sensitive environments such as offices, hospitals, and labs.
Oil-Free Design: No oil means safer operation with no risk of oil leaks or environmental contamination.
High Efficiency: Low no-load and load losses, improving energy conservation and reducing operational costs.
Protects Sensitive Equipment: Filters electrical noise, voltage surges, and harmonic distortion, ensuring stable power for sensitive electronics and machinery.
Minimal Maintenance: Dry-type construction eliminates the need for oil checks, replacements, and frequent maintenance, lowering long-term costs.
Safe Indoor Use: The oil-free, flame-retardant design makes it suitable for indoor installations in commercial and industrial environments.
Improved Power Quality: Provides a clean, stable power supply that prevents system disruptions, enhancing the reliability and performance of connected devices.
Reduced Operational Costs: Lower energy consumption due to high efficiency and reduced maintenance requirements, resulting in cost savings over time.
High Short-Circuit Strength: Withstands thermal and dynamic stresses during faults, ensuring protection and durability in industrial settings.
Flexible Voltage Configuration: Can be customized to meet specific voltage requirements, making it adaptable to various applications.
Meets International Standards: Fully compliant with IEC, CE, and GB standards, ensuring top-notch safety and performance.
Long Service Life: Designed to last over 20 years, providing reliable performance and low operational costs over its lifetime.
Compact Design: The compact form factor saves space, making it suitable for installations with limited space while maintaining robust performance.
Industrial Equipment: Power distribution for manufacturing and automation systems.
Data Centers: Ensures clean and stable power supply for servers and network equipment.
Medical Equipment: Provides isolated and stable power to sensitive medical devices.
Communication Systems: Ideal for communication base stations and control systems.
Commercial Buildings: Used for electrical distribution in offices and high-rise buildings.