Rated capacity (KVA) | Vector Group | Voltage Combination | | | No-load loss | Load loss | No-load current | lmpedance | ||
| | HV | Tapping range | LV | | | | | ||
30 | Yyn0 / Dyn11 | 10 6.3 6 | ±5% ±2X2.5% (+3/-1)X2.5% | 0.4 | 135 | 640 | 2 | 4.0 | ||
50 | | | | | 195 | 900 | 2 | | ||
80 | | | | | 265 | 1240 | 1.5 | | ||
100 | | | | | 290 | 1410 | 1.5 | | ||
125 | | | | | 340 | 1660 | 1.3 | | ||
160 | | | | | 385 | 1910 | 1.3 | | ||
200 | | | | | 445 | 2270 | 1.1 | | ||
250 | | | | | 515 | 2480 | 1.1 | | ||
315 | | | | | 635 | 3120 | 1 | | ||
400 | | | | | 705 | 3590 | 1 | | ||
500 | | | | | 835 | 4390 | 1 | | ||
630 | | | | | 965 | 5290 | 0.85 | | ||
630 | | | | | 935 | 5360 | 0.85 | 6.0 | ||
800 | | | | | 1090 | 6260 | 0.85 | | ||
1000 | | | | | 1270 | 7310 | 0.85 | | ||
1250 | | | | | 1500 | 8720 | 0.85 | | ||
1600 | | | | | 1760 | 10500 | 0.85 | | ||
2000 | | | | | 2190 | 13000 | 0.7 | | ||
2500 | | | | | 2590 | 15400 | 0.7 | |
Full Electrical Isolation: Prevents interference between primary and secondary circuits.
Vacuum Epoxy Resin Casting: Provides strong insulation, flame retardancy, and moisture resistance.
Low Noise Design: Operating noise ≤ 50dB, perfect for indoor applications.
Oil-Free Construction: Eco-friendly and safe for enclosed spaces.
High-Grade Core Material: Made with low-loss cold-rolled silicon steel.
Protects Sensitive Equipment: Filters voltage disturbances and suppresses harmonics.
Reduces Maintenance Needs: No oil replacement, fewer failures.
Safe for Indoor Use: No risk of oil leakage or fire hazard.
Improves System Reliability: Enhances power quality and stability.
Easy Installation: Compact and accessible terminal design.
High Short-Circuit Strength: Withstands dynamic and thermal stress during faults.
Customizable Voltage Options: Supports various input/output configurations.
IEC & CE Certified: Built to meet global safety and efficiency standards.
Long Service Life: Durable insulation system ensures 20+ years of operation.
Adaptable for Harsh Environments: Optional IP23 protection grade.
Precision machine tool power supply
Industrial automation control systems
Hospitals & medical equipment
Laboratories and research centers
High-rise building distribution panels
CNC equipment, elevators, and smart control systems