2400kV AC Lightning Impulse Voltage Withstand Test System
|
Stable Waveform: The control and measurement system utilizes a mature domestic solution. Its core component is the Mitsubishi FX Series programmable logic controller, which implements nearly all control functions through software programming. As a result, the system features a simplified architecture with minimal peripheral circuit boards, ensuring high reliability.
Fully Automated Operation: The control and measurement interface is specifically designed considering the customary workflows of high-voltage testing, offering an intuitive and user-friendly experience. A dedicated program operation interface has been developed to significantly streamline tester operations and effectively prevent human error.
Extended Service Life: This lightning impulse voltage generator test system is built with advanced technology, superior craftsmanship, and high-quality materials, ensuring long-term operational reliability with a lifespan exceeding 20 years. It also maintains low routine operating costs.
Compact Main Structure: The generator adopts a modern compact design, characterized by low inherent inductance and simplified waveform adjustment.
Integrated Measurement and Control Design: The system employs a fiber-optic control transmission system to connect the control measurement equipment with the high-voltage main unit. This design effectively mitigates risks associated with elevated ground potential during high-voltage tests and eliminates electromagnetic interference from control wiring, significantly enhancing overall system reliability.

|
Chopping gap, performing cut-wave tests.
|
Shunt resistor,the current waveform can be correctly recorded in the tests.
|
|
Specifications:
|
||
|
1
|
Impulse voltage grade
|
100kV-7200kV
|
|
2
|
Standard lightning wave
|
1.2±30%/50±20%µS
|
|
3
|
Peak oscillation
|
5%
|
|
4
|
Standard switching wave
|
250±20%/2500±60%µS
|
|
5
|
Virtual front time of oscillating lightning wave
|
15µS
|
|
6
|
Virtual front time of oscillating switching wave and virtual front time of oscillating switching impulse wave
|
15µS-1µS
|
|
7
|
The minimum output voltage
|
10%Un
|
|
8
|
Charging voltage instability
|
1%
|
|
9
|
Synchronizing range
|
20%
|
|
10
|
Synchronous discharge error rate
|
2%
|
|
11
|
Ignition range
|
10%-100%
|
|
12
|
Working time
|
70%UN Discontinuous work(charge-discharge 300s/time)
|
|
70%nn Continuous work(charge-discharge 120s/time)
|
||
|
13
|
Generator efficiency
|
lightning wave (no load)-----90%
|
|
14
|
Time to chopping
|
2-5µS
|