LPM 40-760/4/LPM 50-760/4 is a T2 level power surge protector specifically designed for wind power generation systems. It is engineered to withstand the high-voltage requirements of wind power systems (690Vac nominal voltage), providing reliable protection against transient overvoltages caused by lightning strikes and power grid fluctuations.
|
Product Features
|
|
● Independent integrated module for each pole
|
|
● Built-in ultra-low temperature release mechanism
|
|
● Equipped with indication windows and remote signaling contacts
|
Application scenarios

Product Specification

| Standards | IEC 61643-11 |
| SPD type | T2 |
| Models |
LPM 40-760/4 LPM 50-760/4 |
| Nominal operating voltage Un | 690Vac(50Hz) |
| Maximum continuous operating voltage Uc | 760Vac(50Hz) |
| Nominal discharge current (8/20μs)In | 40kA/50kA |
| Maximum discharge current (8/20μs) Imax | 80kA/100kA |
| Voltage protection level In@Up | ≤3.0kV/≤3.2kV |
| Response time tA | ≤25ns |
| Protection Circuit | L1,L2,L3,N-E |
Mechanical parameters
| Installation method | DIN Rail 35mm |
| Screw torque | 5N*m |
| Strip length |
12mm
|
| Wiring cross-sectional area | 2.5mm²-32mm² |
| Product size | 90mmx144mmx68mm |
| Shell material and flame retardant grade | Mineral nylon PA6, V0 |
| Deterioration indication | Window red: Fail |
| Remote signaling contact type | Normally closed and normally open switching contacts |
| Remote signaling contact switching ability | 125Vac/1A,125Vdc/0.2A |
| Maximum connection capacity of remote signaling | 2.5mm² |
| Installation position | Indoor |
| Degrees of protection provided by enclosure | IP20 |
| Temperature range | -40℃…+80℃ |
| Humidity range | Relative humidity ≤ 95% (max 40 ℃) |
Notices
● Confirm the wind power system voltage matches 690Vac(50Hz) before installation.
● Use wiring with cross-sectional area 2.5mm²-32mm² and tighten screws to 5N·m torque.
● Regularly check the indication window—replace the product immediately if it turns red (failure status).
● Ensure the grounding system meets wind power industry requirements (ground resistance ≤4Ω).
● The product is designed for indoor use in wind turbine control cabinets; avoid outdoor exposure.
● Select the appropriate model based on the required discharge current (40kA/50kA).
FAQ
Q1: What is the maximum continuous operating voltage of this product?
A1: The maximum continuous operating voltage (Uc) is 760Vac, suitable for 690Vac wind power systems.
Q2: Can it be used in solar power systems?
A2: No, this model is designed for high-voltage AC wind power systems. For solar PV systems, choose LPM PV series DC SPDs.
Q3: What is the function of the built-in ultra-low temperature release mechanism?
A3: It ensures the product operates safely in low-temperature environments (-40℃) and disconnects faulty modules to avoid hazards.