Specifications
Brand Name :
LLH
Model Number :
LPM 40-385/4
Place of Origin :
Guangdong Province.China
MOQ :
1 piece
Payment Terms :
L/C,D/A,D/P,T/T,Western Union
Supply Ability :
5000-10000 pieces/mouth
Delivery Time :
7-15 days
Packaging Details :
box
Price :
$28/pcs
Model :
LPM 40-385/4 / LPM 50-385/4 / LPM 80-385/4 / LPM 100-385/4
SPD Type :
T2 (IEC 61643.11)
Nominal Operating Voltage (Un) :
230Vac(50Hz)
Maximum Continuous Operating Voltage (Uc) :
385Vac(50Hz)
Nominal Discharge Current (In) :
40kA/50kA/80kA/100kA
Maximum Discharge Current (Imax) :
80kA/100kA/160kA/200kA
Voltage Protection Level (Up) :
≤2.0kV / ≤2.2kV / ≤2.2kV / ≤2.2kV
Response Time :
≤25ns
Description

LPM 40-385/4 Series is a T2 level power surge protector designed for three-phase power supply systems. It is specifically tailored for industrial and commercial power systems, providing reliable protection against transient overvoltages caused by lightning strikes and power grid fluctuations.

Product features

● Independent integrated module for each pole
● Built-in ultra-low temperature release mechanism
● Equipped with indication windows and remote signaling contacts
● Application scenarios:Suitable for installation in LPZ 0B-1 and subsequent lightning protection zones, used as lightning arrester for wind powergeneration systems.


Product Features


3 Phase Whole House Surge Protection Device 220V 40kA 50KA 80kA 100KA DIN Rail

Standards IEC 61643-11
SPD type T2
Models

LPM 40-385/4

LPM 50-385/4

LPM 80-385/4
LPM 100-385/4
Nominal operating voltage Un 230Vac(50Hz)
Maximum continuous operating voltage Uc 385Vac(50Hz)
Nominal discharge current (8/20μs)In 40kA/50kA/80kA/100kA
Maximum discharge current (8/20μs) Imax 80kA/100kA/160kA/200kA
Voltage protection level In@Up ≤2.0kV/≤2.2kV/≤2.2kV/≤2.2kV
Response time tA ≤25ns
Protection Circuit L1,L2,L3,N-E

Mechanical parameters

Installation method DIN Rail 35mm
Screw torque 5N*m
Strip length 12mm
Wiring cross-sectional area 2.5mm²-32mm²
Product size 90mmx144mmx68mm
Shell material and flame retardant grade Mineral nylon PA6, V0
Deterioration indication Window red: Fail
Remote signaling contact type Normally closed and normally open switching contacts
Remote signaling contact switching ability 125Vac/1A,125Vdc/0.2A
Maximum connection capacity of remote signaling 2.5mm²

Notices

● Install the SPD in LPZ 0B-1 or subsequent lightning protection zones to ensure effective T2 protection.

● Use wiring with cross-sectional area 2.5mm²-32mm² and tighten screws to 5N·m torque.

● Regularly check the indication windowreplace the product immediately if it turns red (failure status).

● Ensure the grounding system meets requirements (ground resistance 4Ω) for optimal surge diversion.

● Select the appropriate model based on the required discharge current (40kA/50kA/80kA/100kA).

● Avoid using the product beyond the specified temperature (-40~+80) and humidity range.

FAQ

Q1: What is the difference between the models in the series?

A1: The main difference is nominal discharge current (In) and maximum discharge current (Imax): LPM 40-385/4 (40kA/80kA), LPM 50-385/4 (50kA/100kA), LPM 80-385/4 (80kA/160kA), LPM 100-385/4 (100kA/200kA).

Q2: Does the product support remote monitoring?

A2: Yes, it is equipped with normally closed and normally open remote signaling contacts, enabling connection to monitoring systems for remote status tracking.

Q3: What is the function of the built-in ultra-low temperature release mechanism?

A3: It ensures the product operates safely in low-temperature environments (-40) and disconnects faulty modules to avoid hazards.

Q4: Can it be used in 400V three-phase systems?

A4: Yes, with maximum continuous operating voltage 385Vac, it is compatible with 400V three-phase systems (230V phase-neutral).

Q5: What is the flame-retardant grade of the housing?

A5: The housing is made of mineral nylon PA6 with V0 flame-retardant grade, which self-extinguishes within 10 seconds after ignition.

Send your message to this supplier
Send Now

3 Phase Whole House Surge Protection Device 220V 40kA 50KA 80kA 100KA DIN Rail

Ask Latest Price
Watch Video
Brand Name :
LLH
Model Number :
LPM 40-385/4
Place of Origin :
Guangdong Province.China
MOQ :
1 piece
Payment Terms :
L/C,D/A,D/P,T/T,Western Union
Supply Ability :
5000-10000 pieces/mouth
Contact Supplier
video
3 Phase Whole House Surge Protection Device 220V 40kA 50KA 80kA 100KA DIN Rail