| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | PNP | |
| Rated operating distance | 8 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 6.48 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 24 mm x 24 mm x 1 mm |
|
| Reduction factor rAl | 0.38 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.74 | |
| Reduction factor rBrass | 0.47 | |
| Output type | 4-wire | |
| Nominal ratings | ||
| Operating voltage | 5 ... 36 V | |
| Switching frequency | 0 ... 1350 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | ≤ 1 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | max. 20 µA | |
| No-load supply current | ≤ 15 mA | |
| Time delay before availability | ≤ 10 ms | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1255 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Conformity | ||
| PWIS conformity | VDMA 24364-A1/B2/C1/T100°C-W | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| Standards | EN IEC 60947-5-2 | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 36 V | |
| Rated impulse withstand voltage | 500 V | |
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| CCC approval | CCC approval / marking not required for products rated ≤36 V | |
| Marine approval | DNVGL TAA00003AK | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |