Clamp Earth Resistance Tester BE2000C+ (Long Jaw) & BE2100C+ (Round Jaw)
Key Innovation
Major technical breakthrough in ground resistance testing - non-contact, safe, and fast operation with loop resistance measurement capability (no need to disconnect ground wires from rods).
Measurement Capabilities
| Parameter |
Range |
Resolution |
| Resistance |
0.01~1000Ω |
0.001Ω |
| Current |
0.00mA~20.0A |
0.05mA |
Technical Specifications
| Specification |
Details |
| Resistance Accuracy |
± (1%+0.01Ω) |
| Current Accuracy |
± 2.5% ± 1mA |
| Power Supply |
6V DC (4 AA batteries) |
| Data Memory |
99 sets |
| Alarm Threshold |
Resistance: 1-199Ω |
| Alarm Type |
Sound and light indicators |
| Interference Signal Recognition |
Yes |
| Operating Environment |
-20°C to 55°C, 20%-90% RH |
| Display |
4-digit LCD (47×28.5mm) |
| Weight (with batteries) |
Long Jaw: 1160g; Round Jaw: 1120g |
| Tester Dimensions |
Long Jaw: 285×85×56mm; Round Jaw: 260×90×66mm |
| Jaw Size |
Long Jaw: 65×32mm; Round Jaw: Ø32mm |
| Auto Power Off |
5 minutes after startup |
| RS232 Interface |
Optional |
Environmental & Safety Compliance
| Parameter |
Specification |
| External Electric Field |
<1V/m |
| External Magnetic Field |
<40A/m |
| Instrument Safety |
IEC/EN61010-1, IEC/EN6010-2-032 |
| Insulation |
Double insulation |
| Pollution Degree |
Class II |
| Overvoltage Category |
CAT III 150V to ground, Max 20A |
Note: All specifications are subject to change without notice. Please refer to the product manual for the most current information.