| Table 1 | | | | | ||||
| | | | Rated short circuit breaking capacity | | ||||
| | | | Expected current in the last test line(A) | Power factor | ||||
| 63,80,100,125 | 1,2,3,4 | 230/400 | 4000 | 0.45~0.50 | ||||
| Table 2 | | | | | ||||
| Ambient air humidity | I/In | Expected result in the last test | | Start status | ||||
| | | In≤63A | In>63A | | ||||
| | 1.05 | Not trip within 1 hour | Not trip within 2 hours | Cold status starts | ||||
| | 1.30 | Not trip within 1 hour | Trip within 2 hours | Hot status starts | ||||
| | 3.0 | Release time>3s | Release time>5s | Hot status starts | ||||
| | 5.0~10.0(C) | Operate within≤0.1s | | | ||||
| | 10.0~14.0(D) | Operate within≤0.1s | | | ||||