| SPD classification (EN61643-11) | Type 2 | Type 2 | Type 2 | Type 2 | Type 2 |
| SPD classification (IEC61643-11) | Class II | Class II | Class II | Class II | Class II |
| Max. continuous operating voltage Uc | 150V | 275V | 320V | 385V | 440V |
| Nominal discharge current (8/20μs) In | 20kA | 20kA | 20kA | 20kA | 20kA |
| Max. discharge current (8/20μs) Imax | 40kA | 40kA | 40kA | 40kA | 40kA |
| Voltage protection level Up | ≤0.8kV | ≤1.3kV | ≤1.5kV | ≤1.8kV | ≤2.0kV |
| Voltage protection level 5kA Up | ≤0.6kV | ≤1kV | ≤1.2kV | ≤1.3kV | ≤1.5kV |
| Max. backup fuse | 100A gG | 100A gG | 100A gG | 100A gG | 100A gG |
| Response time tA | ≤25ns | ≤25ns | ≤25ns | ≤25ns | ≤25ns |
| Operating temperature range | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
| Operating state / fault indication | green / red | green / red | green / red | green / red | green / red |
| Cross-section area (Min.) | 4mm² | 4mm² | 4mm² | 4mm² | 4mm² |
| Cross-section area (Max.) | 35mm² | 35mm² | 35mm² | 35mm² | 35mm² |
| For mounting on | 35mm Din rail |
| Enclosure material | Thermoplastic UL94-V0 |
| Degree of protection | IP20 | IP20 | IP20 | IP20 | IP20 |