The LKSR series are closed-loop, multi-range current transducers with voltage output, designed for the electronic measurement of DC, AC, and pulsed currents. They offer galvanic separation between the primary and secondary circuits, featuring a unipolar supply voltage and a compact design for PCB mounting. These transducers provide very low offset drift, excellent dv/dt immunity, and are compatible with the CKSR footprint. They are suitable for applications such as AC variable speed and servo motor drives, static converters, battery-supplied applications, Uninterruptible Power Supplies (UPS), Switched Mode Power Supplies (SMPS), power supplies for welding, and solar inverters. The series is certified according to various IEC and UL standards.
| Parameter | Symbol | Unit | LKSR 6-NP (Typ) | LKSR 15-NP (Typ) | LKSR 25-NP (Typ) | Comment |
|---|---|---|---|---|---|---|
| Primary nominal RMS current | IP N | A | 6 | 15 | 25 | Apply derating according to fig. 21, 22, 23 |
| Primary current, measuring range | IP M | A | -20 to 20 | -51 to 51 | -85 to 85 | |
| Number of primary turns | NP | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | ||
| Supply voltage | UC | V | 4.75 to 5.25 | 4.75 to 5.25 | 4.75 to 5.25 | |
| Current consumption | IC | mA | 17 + 20 * (NP/2000) | 17 + 20 * (NP/2000) | 17 + 20 * (NP/2000) | NS = 2000 turns |
| Reference voltage @ IP = 0 A | Vref | V | 2.485 to 2.515 | 2.485 to 2.515 | 2.485 to 2.515 | Internal reference |
| Output voltage @ IP = 0 A | Vout | V | Vref | Vref | Vref | |
| Electrical offset voltage | VO E | mV | -5 to 100 | -1.75 to 1.75 | -1 to 1 | 100 % tested |
| Temperature coefficient of Vref | TCVref | ppm/K | 70 | 70 | 70 | Internal reference |
| Temperature coefficient of Vout @ IP = 0 A | TCVout | ppm/K | 14 ppm/K of 2.5 V | 6 ppm/K of 2.5 V | 4 ppm/K of 2.5 V | -40 C 105 C |
| Theoretical sensitivity | Gth | mV/A | 104.2 | 41.67 | 25 | 625 mVIP N |
| Sensitivity error | G | % | -0.2 to 0.2 | -0.2 to 0.2 | -0.2 to 0.2 | 100 % tested |
| Temperature coefficient of G | TCG | ppm/K | 40 | 40 | 40 | -40 C 105 C |
| Linearity error | L | % of IP N | -0.1 to 0.1 | -0.1 to 0.1 | -0.1 to 0.1 | |
| Magnetic offset current (10 IP N) referred to primary | IO M | mA | -25 to 25 | -45 to 45 | -60 to 60 | |
| Output RMS voltage noise spectral density (100 100 kHz) referred to primary | eno | V/Hz | 7 | 3.5 | 1.8 | |
| Reaction time @ 10 % of IP N | tra | s | 0.3 | 0.3 | 0.3 | RL = 1 k, di/dt = 50 A/s |
| Step response time to 90 % of IP N | tr | s | 0.4 | 0.4 | 0.4 | RL = 1 k, di/dt = 50 A/s |
| Frequency bandwidth (1 dB) | BW | kHz | 300 | 300 | 300 | RL = 1 k |
| Overall accuracy | XG | % of IP N | 1.25 | 0.75 | 0.75 | |
| Accuracy | X | % of IP N | 0.5 | 0.5 | 0.5 | |
| Absolute maximum ratings: Maximum supply voltage | UC max | V | 7 | 7 | 7 | |
| Absolute maximum ratings: Maximum primary conductor temperature | TB max | C | 110 | 110 | 110 | |
| Absolute maximum ratings: Maximum primary current | IP max | A | 20 IPN | 20 IPN | 20 IPN | |
| Insulation coordination: RMS voltage for AC insulation test, 50 Hz, 1 min | Ud | kV | 4.3 | 4.3 | 4.3 | |
| Insulation coordination: Impulse withstand voltage 1.2/50 s | W | kV | 8 | 8 | 8 | |
| Insulation coordination: Insulation resistance | RINS | G | 18 | 18 | 18 | measured at 500 V DC |
| Insulation coordination: Comparative tracking index | CTI | 600 | 600 | 600 | ||
| Environmental: Ambient operating temperature | TA | C | -40 to 105 | -40 to 105 | -40 to 105 | |
| Environmental: Ambient storage temperature | TS | C | -55 to 125 | -55 to 125 | -55 to 125 | |
| Mechanical: Mass | m | g | 10 | 10 | 10 |