Modular UPS Systems 60KVA UPS Three Phase Ups 380v N+X Redundancy DSP Control
25kVA 50kVA UPS Power Module, Double DSP control
Scalable from 20 kVA to 300kVA.
Modular, hot-swappable, field-replaceable STS, Monitor, UPS module
RSUN PM Series delivers scalable power protection through a modular, high-efficiency UPS design. Featuring dual-DSP control, it ensures precise operation, fast fault detection, and real-time power regulation.
Advanced power electronics, including current-sharing rectifiers, intelligent inverters, and multi-level control, provide robust performance under dynamic load conditions.
Designed for evolving infrastructures like data centers, finance, and automation, the PM Series supports flexible configuration, system-level redundancy, and simplified maintenance, ensuring uninterrupted operations and long-term energy savings.
FEATURES:
SPECIFICATIONS:
| Model | PM60 | PM120 | PM200 | PM300 | |
| Rated Capacity | 60kVA | 120kVA | 200kVA | 300kVA | |
| INPUT | |||||
| Wiring Method | 3 Phase+N+PE | ||||
| Rated Voltage | 380/400/415VAC(line-line) | ||||
| Rated Frequency | 50/60Hz | ||||
| Voltage Range | 304VAC ~ 478VAC (line-line) full load, 304VAC ~ 228VAC (line-line) Load derating linearly from 100% to 80% | ||||
| Frequency Range | 40Hz~70Hz | ||||
| Power Factor | >0.99 | ||||
| THD | THD<3%(linear full load), THD<5%(non-linear full load) | ||||
| BYPASS | |||||
| Rated Voltage | 380/400/415VAC(line voltage) | ||||
| Voltage Range | Factory setting -20% ~ +15%, settable, upper limit:+10%, +15%,+20%,+25%, lower limit:-10%,-15%, -20%, -30%,-40% | ||||
| Frequency Range | Rated frequency 50/60Hz, frequency range can be set ±1Hz ,±3Hz ,±5Hz | ||||
| Overload Capacity | 110% for long run, >150% for 200ms | ||||
| BATTERY | |||||
| Battery Voltage | ±192VDC ( 360 ~ 528VDC, 30 ~ 44 block settable, factory setting 32 block) | ||||
| Charging Capacity | 15%* total capacity | ||||
| Voltage Accuracy | ±1% | ||||
| OUTPUT | |||||
| Rated Voltage | 380V/400V/415V(line-line) | ||||
| Rated Frequency | 50/60Hz | ||||
| Power Factor | 1 | ||||
| Voltage Accuracy | ≤±1.0%@ balanced load, ≤±5.0%@ unbalanced load | ||||
| Frequency Accuracy | 50/60Hz±0.01% | ||||
| Frequency Tracking Range | Settable, ±0.5Hz~±5Hz, factory setting ±3Hz | ||||
| THD | THDu≤2%(100% linear load), THDu≤4%( nonlinear load) | ||||
| Three-phase Phase Accuracy | 120°±1° | ||||
| Crest Factor | 3:01 | ||||
| Overload |
<105% long run, <110% 60mins, 110 ~ 125% 10mins, >125 ~ 150% 1mins, >150% 200ms |
||||
| SYSTEM | |||||
| System Efficiency | ≥96%@ double conversion mode ,≥98%@ECO mode | ||||
| Display | Touch screen + LED | ||||
| Wiring | Support top in and bottom in | Top in | |||
| Standard | IEC62040-1-1; IEC62040-2; IEC62040-3 | ||||
| Protection Class | IP20 | ||||
| Feeder Protection | Standard: isolating switch, optional: fuse | ||||
| Communication | RS232/ RS485/ Modbus/SNMP (optional) / dry contact (optional) | ||||
| Optional | Dust-proof net, lightning protection module, LBS cable, earthquake-proof components, temperature and humidity sensor | ||||
| Working Condition | Temperature :0 ~ 40℃, humidity:0~95%( no condensation) | ||||
| Noise | <60dB@1 meter | ||||
| Altitude | <1000 meters, no derating, >1000 meters, derating 1% if every 100 meters increased | ||||
| Cabinet Type | 4 Modules | 7 Modules | 12 Modules | ||
| SIZE | |||||
| System W x D x H (mm) | 600 x 890 x 1200 | 600 x 960x 1600 | 600 x 1010 x 2000 | ||
| Module W x D x H (mm) | 440 x 690 x 86 ( 2U) | ||||
| WEIGHT | |||||
| System(kg) | 140 | 185 | 250 | 270 | |
| Module(kg) | 25 | ||||
APPLICATIONS:
• IDC, cloud & computing centers
• Telecom infrastructure
• Financial institutions
• Government & healthcare IT
• Industrial control and smart factories