UPS 500KVA Modular UPS systems up to 1200kVA Uninterrupted Power Supply 50KVA modules, 50kVA / 60kVA UPS Power Module, Double DSP control
Modular, hot-swappable, field-replaceable STS, Monitor, UPS module
The RSUN PM Series is a high-efficiency modular UPS solution designed for mission-critical applications. Featuring dual high-speed DSP controllers and a true online double-conversion architecture, it integrates power rectification, charging, filtering, and inversion in a unified, intelligent platform.
Its advanced control features, such as dynamic current-sharing rectifiers, multi-level distributed logic, and three-level inverter topology, enable accurate load management, robust fault isolation, and real-time system coordination. With scalable modularity and N+X redundancy, the PM Series supports flexible capacity upgrades while ensuring system resilience, low MTTR, and optimal TCO for data centers and industrial facilities.
FEATURES:
SPECIFICATIONS:
| Model | PM200 | PM300 | PM500 | PM600 | PM840 | PM1000 |
| System Capacity | 200kVA | 300kVA | 500kVA | 600kVA | 840kVA/840kW | 1000kVA/1000kVA |
| Power Module Capacity | 50kVA | 50kVA | 50kVA | 50kVA | 60kVA/60kW | 62.5kVA/62.5kW |
| No. of Modules | 4 | 6 | 10 | 12 | 14 | 16 |
| Main | ||||||
| Input Wiring | 3Ph+N+PE | |||||
| Rated Voltage | 380/400/415VAC (line-line) | |||||
| Input Power Factor | >0.99 | |||||
| Total Harmonic Distortion | THDi<3% for linear full load, THDi<5% for nonlinear full load | |||||
| Voltage Range | 304~478Vac(line-line) 100% load; | |||||
| 228V~304Vac (line-line) load derated from 100%-75% linearly | ||||||
| Input Frequency | 40Hz~70Hz | |||||
| Bypass | ||||||
| Rated Voltage | 380/400/415VAC (line-line) | |||||
| Voltage Range | Default Range +15%~-20%(+10%,+15%,+20%,+25%, +25%-10%,-15%, -20%, -30%,-40% can be set) | |||||
| Input Frequency | ±1Hz,±3Hz,±5Hz can be set | |||||
| Battery | ||||||
| Input Voltage | ±240VDC (the number of batteries can be selected from 30 to 44) | |||||
| Charging Power | 20% * Power Module | |||||
| Charging voltage accuracy | ±1% | |||||
| Output | ||||||
| Rated Voltage | 380/400/415VAC (line-line) | |||||
| Rated Frequency | 50/60Hz | |||||
| Power Factor | 1 | |||||
| Voltage Accuracy | ≤±1.0%@Steady ;≤±5.0%@ Transient | |||||
| Dynamic response | <5% (20% - 80% -20% Step load) | |||||
| Dynamic recovery time | < 20ms (0% - 100% -0% Step load) | |||||
| THDu | THDu <1%(linear load),THDu<5%( non linear load), | |||||
| Overload Capacity | 110% overload for 60 min; 125% overload for 10 min; 150% overload for 1 mins; | |||||
| >150% overload for 200ms | ||||||
| System | ||||||
| Efficiency | >96.5% (Dual Switch mode) | |||||
| Display | 10.4 inch Touch Screen+LCD+LED | |||||
| IP | IP20 | |||||
| Environment | Operating Temperature: 0-40℃;Relative Humidity 0-95%(No condensing) | |||||
| Noise | <55dB@1 meter away | |||||
| Dimension ( WxDxH mm) and Weight (kg) | ||||||
| Cabinet Dimension | 600*850*2000 | 600*1100*2000 | 1000*1000*2000 | 1000*1000*2000 | 1800*850*2000 | 3600*1000*2000 |
| Module Dimension | 440*720*130 (3U) | 440*720*174 (4U) | ||||
| Cabinet Weight (KG) | 190 | 270 | 450 | 530 | 960 | 1100 |
| Module Weight (KG) | 39 | 39 | 39 | 39 | 39 | 39 |
APPLICATIONS:
This UPS system is purpose-built for critical sectors requiring uninterrupted, high-quality power delivery:
• Cloud data centers, colocation facilities, and edge computing environments
• Telecommunications backbones, including ISPs, mobile base stations, and core routing nodes
• Financial networks involving banking, securities trading, and payment gateways
• Government infrastructure for tax systems, digital public services, and secure IT networks
• Hospital IT, medical imaging systems, and electronic health record environments
• Industrial control systems such as PLC / SCADA, robotics, and automated production lines
• Precision electronics, laboratory equipment, and sensitive instrumentation setups