HIOKI AC Clamp Meter CM4141-50
Technical Specifications
| Parameter |
Specifications |
| AC Current Range |
60.00 A to 2000 A, 3 ranges (45 to 1 kHz, true RMS rectified)
Basic accuracy 45-66 Hz: ±1.5% rdg. ±0.08 A (range 60 A) |
| Crest Factor |
Measuring range 60.00 A: 2.5 (above 50.00 A is below 60.00 A)
Measuring range 2000 A: 1.5 (below 2000 A) |
| DC Voltage Range |
600.0 mV to 1000 V (600.0 V to 2000 V when using P2000) |
| AC Voltage Range |
6.000 V to 1000 V, 4 ranges (15 to 1 kHz, true RMS rectified)
Basic accuracy 45-66 Hz: ±0.9% rdg. ±0.003 V (at 6V) |
| AC + DC Voltage Range |
6.000 V to 1000 V, 4 ranges
Basic accuracy DC, 45-66 Hz: ±1.0% rdg. ±0.013 V (at 6V) |
| Resistance Range |
600.0 Ω to 6,000 MΩ, 5 measuring ranges
Basic accuracy: ±0.7% rdg. ±0.5 Ω (at 600 Ω) |
| Electrostatic Capacitance Range |
1.000 μF to 1000 μF, 4 measurement ranges
Basic accuracy: ±1.9% rdg. ±0.005 μF (at 1 μF) |
| Frequency Range |
Voltage: 9.999 Hz to 999.9 Hz, 3 ranges
Current: 99.99 Hz and 999.9 Hz, 2 ranges
Basic accuracy: ±0.1% rdg. ±0.01 Hz (at 99.99 Hz) |
| Temperature (K) |
-40.0 to 400.0 ˚C
Accuracy: ±0.5% rdg. ±3.0 ˚C + temperature probe accuracy |
Additional Features
Harmonic Measurement
When installing Z3210: Can measure harmonic level/content/total harmonic distortion up to 30th order in current and display using GENNECT Cross application software.
- Continuity check
- Diode check
- Automatic AC/DC judgment function (voltage only)
- Display of maximum/minimum/average/peak maximum/peak minimum values
- Low-pass filter function
- Display value hold
- Backlight
- Automatic power saving
- Buzzer sound
- Zeroing
Environmental & Physical Specifications
Dustproof and Waterproof
IP20: Measures voltage or current in hazardous live conductors when completely dry
IP50: Measures resistance or current in insulated conductors when stored or in completely dry condition
Do not measure under wet conditions
Power Supply
2 x AAA alkaline batteries (LR03)
Provides approximately 48 hours of use (without Z3210 installed)
Provides approximately 24 hours (with Z3210 installed and wireless communication enabled)
Other conditions: AC 100 A measurement, LCD backlight OFF, 23°C (reference value)
Physical Dimensions
Measurable conductor diameter: φ 55 mm
Jaw size: 82 W * 11 D mm (D is within 44 mm of the jaw tip)
Minimum cross-sectional dimensions of jaws: 11 mm (within 44 mm of the jaw tip)
Volume and weight: 65 W * 247 H * 35 D mm, 300 g
Included Accessories
- Test cable L9300 *1
- Carrying bag C0203 *1
- AAA alkaline batteries (LR03) *2
- Instruction manual *2
- Usage precautions *1
Accuracy guaranteed for 1 year, accuracy guaranteed for 1 year after adjustment