Intelligent DC Power Supply System with Busbar Voltage Loss Compensation, Battery Health Monitoring, and Modularized Power Supply Unit
The intelligent DC power supply system integrates an AC distribution unit, charging module, feeder unit, battery bank, monitoring unit, voltage and current monitoring instruments, insulation monitoring device, silicon-based voltage reduction circuit, and battery management unit. It serves as a critical component of substation power systems and power plants, providing power for automatic control, power equipment, relay protection, instrumentation, signaling, communication, and emergency lighting systems.
The DC power supply system is applied in large, medium, and small power plants as well as substations, providing the necessary DC power for high-voltage switch operations (opening/closing), relay protection, automatic control, emergency lighting, illumination, and signaling during both normal operation and fault conditions.
It also serves industries such as metallurgy, railways, mining, petrochemicals, postal services, telecommunications, healthcare, banking, hotels, high-rise buildings, and computer networks. This product complies with the JB/T 57774-2000 standard "General Technical Requirements and Safety Requirements for DC Power Equipment in Power Systems".
| Order Number | Project | Technical Requirement |
|---|---|---|
| 1 | AC Input Power Source | 323V~456V |
| 2 | AC Input Frequency | 45Hz~55Hz |
| 3 | Power Factor | >0.92 |
| 4 | Asymmetry of the AC Input Voltage | ≤5% |
| 5 | Percentage of Each Harmonic Current Component (2nd to 19th Order) | <30% |
| 6 | Nominal Voltage of the DC Power Supply System (Un) | 110V(220V) |
| 7 | Normal Operating Voltage of the DC Control Busbar | 115.5V(231V) |
| 8 | Charging Voltage Adjustment Range | (90%~125%)Un |
| 9 | DC Control Bus Voltage Range | (85%~112.5%)Un |
| 10 | DC Power Bus Voltage Range | (87.5%~17.5%)Un |
| 11 | Steady Flow Accuracy | ≤0.5% (when operating at 20–100% of the rated output current) |
| 12 | Voltage Stabilization Accuracy | ≤0.5% (when outputting rated current from 0% to 100%) |
| 13 | Flow Distribution Imbalance | ≤±3% |
| 14 | Ripple Factor | ≤0.1% |
| 15 | Productiveness | >93% |
| 16 | Noise | ≤55 dB (at a distance of 1 m from the device) |
| 17 | Cooling Method | Use natural cooling or forced air cooling |
| 18 | Time Interface | IRIG-B code and software synchronization |
| 19 | Communication Interface | RS485/RS232 communication interfaces and Ethernet communication interfaces |
| 20 | Communication Protocol | IEC 103, IEC 61850, MODBUS protocol |