Intelligent Integrated Power Supply System with Comprehensive Equipment Status Visualization Intelligent Fault Analysis and Modularized Power Supply Unit
Hongyi Technology's intelligent integrated power system delivers three core functionalities: comprehensive equipment status visualization through unified information transmission architecture and data models, trend analysis of critical parameters for key AC/DC power equipment with fault early warning diagnostics and self-healing recovery, and online remote operation and maintenance with smart management tools for equipment risk assessment and condition-based maintenance.
This intelligent integrated power system provides safe, reliable, and intelligent power solutions for AC/DC equipment, including 380V/220V AC power, 220V/110V DC power, and -48V communication-grade DC power. It is suitable for substations, distribution centers, power plants, and other applications requiring AC/DC power supply.
| Substation Classification | Subsystem Name | System Solution Description |
|---|---|---|
| 35KV | AC Power Supply System | ATS Switching, Single Bus Output |
| 35KV | DC Power Supply System | One charge per cycle; single-busbar wiring configuration |
| 35KV | UPS Power Supply System | 3KVA single UPS module |
| 35KV | Power Supply System for Communications | DC/DC communication power module connected to DC bus |
| 110KV | AC Power Supply System | Dual ATS switching, dual bus output |
| 110KV | DC Power Supply System | One charge per cycle; single-busbar wiring configuration |
| 110KV | UPS Power Supply System | Two 5 KVA dual UPS modules configured for hot backup or N+1 operation |
| 110KV | Power Supply System for Communications | DC/DC communication power module connected to DC bus |
| 220KV | AC Power Supply System | Dual ATS switching, dual bus output, or two incoming lines with one common bus |
| 220KV | DC Power Supply System | Two charging cycles; two bus sections |
| 220KV | UPS Power Supply System | Two 7.5 KVA dual UPS modules configured for hot backup or N+1 operation |
| 220KV | Power Supply System for Communications | DC/DC communication power modules connected to two busbars |
| 500KV | AC Power Supply System | Dual ATS switching, dual bus output, or two incoming lines with one common bus |
| 500KV | DC Power Supply System | Two charges for two power outputs, or three charges for two power outputs; two-section busbar configuration |
| 500KV | UPS Power Supply System | Two 15 KVA dual UPS modules configured for hot standby or parallel N+1 operation |
| 500KV | Power Supply System for Communications | DC/DC communication power modules connected to two busbars |