American Style 15kV Two-Pass Insulation Bushing for Ring Cabinet RMU
Type: ADG-15/200
The double-pass bushing is used in the case of variable high-voltage lead-in line, and the elbow arrester is installed when
the transformer system is provided with over-voltage protection. It is also possible to change the box terminal connection to
the ring network connection. For one-piece copper forging parts, internal structure of conductive resistance is smaller than
other similar welding type two-way bushing 100 μΩ running at lower temperature. Unique torque-limiting construction ensures
that the bolts in the socket are not broken. Built-in insertion reinforcing design can ensure 400N of insertion and extraction force, t
he use is safe and reliable, won’t loose out of the accident.
American Type 200A Detachable Connector Performance Parameters
|
Rated voltage |
15kV |
|
Rated current |
200A |
|
Power frequency withstand voltage (5mins) |
39kV |
|
Partial discharge of 15kV |
≤5pC |
|
Thermostable current |
16kA |
|
Dynamic stable current (10ms) |
40kA |
American Application Standard for Detachable Connector