EK6-12/40.5kv Indoor AC High Voltage Earthing Switch A-B-B Grounding Switch
1.Product introduction
Earthing switches of series EK6 are determined for indoor in stallation and conform to the requirements of
GB1985 and IEC 62271-102. They are fitted with snap-action operating mechanisms for positive high-speed
closing and sufficiently dimensioned to conduct the rated short-circuit making current when closed under load.
The speed of the snap-action closing operation is independent controls. The earthing switches are supplied
as kits with a pre-assem bled active part and correspon ding earthing con tacts supplied loose. Correct in
stallation of these parts in a switchgear panel results in a functioning earthing switch. Routine tests toGB1985
and IEC 62271-102 are to be carried out at site accordingly.
2. Normal Using Ambient Conditions
(a) ambient air temperature: upper limit +40℃;lower limit – 25℃
Remark: allow to store and transport under – 30℃
(b) altitude limit: under 1000m
(c) relative humidity: under 90%
(d) earthquake intensity : not higher than class Ⅷ
(e)the place should be without fire,explode danger, serious dust, chemical corrosion and strong shork.
3. Technical Parameters
|
|
Rated voltage (kV) |
Highest working voltage (kV) |
4S rated short time withstand current(kA) |
Rated dynamic stable current (peak value) (kA) |
Making current (peak value) (kA) |
Pole center distance (mm) |
Making speed (m/s) |
Main circuit contact resistance (μΩ) |
|
EK6-12/31.5-210 |
10 |
12 |
31.5 |
80 |
80 |
210 |
>6 |
<120 |
|
EK6-40.5/31.5-280 |
35 |
40.5 |
31.5 |
80 |
80 |
280 |
>6 |
<120 |