High Voltage Switchgear 12kv Solid Insulated Ring Main Unit RMU For Indoor with SF6 free
Since 1 990s, with the accelerating progress of urbanization and continual improvement of power supply reliability,theoverhead line is replacing by buried cable and indoor switching station replacing by outdoor switching station. The smal.touchable, allinsulated, flood-control, and maintenance-free ring main units are rapidly developed and widely used in differenplaces with reliable power distribution system, such as the urban commercial center, industrial concentration district, airport.electrified rallwav and expresswav etct can be single used indoor and outdoor, as well as be integrated in prefabricatecsubstation.
MKS series solid-insulated ring main units comprehensively introduces advanced production faclity and manufacturingtechnology, implementing localized production, greatly reducing the manufacturing costs, shortening delivery period, and itreceives a favorable respnse after the launch.
Product Model: MKS-12
Rated Specification: 12 kV – 630 A
Core Unit Configuration: Upper-isolation / Lower-isolation
Altitude Classifications: ≤ 1500 m / > 1500 m
Operation Mode: Manual / Electric
Rated Short-circuit Breaking Current: 20 kA / 25 kA
Integral Earthing Switch: With / Without
Control Voltage: 24 V / 48 V / 220 V (110 V on request)
Standard Configuration: Vacuum circuit-breaker / load-break switch , three-position disconnector
| Item | Unit | load switch cell | circuit breaker cell | Fuse Combining cell | |||||
| Rated voltage | kV | 12 | 12 | 12 | |||||
| Rated current | A | 630 | 630 | depend on the fuse | |||||
| Rated frequency | Hz | 50 | 50 | 50 | |||||
| Rated insulation level | 1 min power frequency withstand voltage (phase to phase & phase to ground) | kV | 42 | 42 | 42 | ||||
| 1min Power Frequency Withstand Voltage (lsolation Gap) | 48 | 48 | 48 | ||||||
| RatedPower Frequency Withstand Voltage(Control &Auxiliary Circuits) | 2 | 2 | 2 | ||||||
| Lightning Impulse Withstand Voltage(Phase-to-Phase &Phase-to-Ground) | 75 | 75 | 75 | ||||||
| Lightning Impulse Withstand Voltage (lsolation Gap) | 85 | 85 | 85 | ||||||
| Short-Circuit Breaking Current | kA | 20 | 20 | depend on the fuse | |||||
| Rated Short-Circuit Making Current | kA | 50 | 50 | depend on the fuse | |||||
| Rated Short-Time Withstand Current | kA | 20 | 20 | / | |||||
| Rated Short-Time Duration | s | 4 | 4 | / | |||||
| Rated Peak Withstand Current | kA | 50 | 50 | / | |||||
| Rated transfer current | A | / | / | 3150 | |||||
| Rated Operating sequence | / | O-0.3s-CO-180s-CO | / | ||||||
| Mechanical life | Circuit breaker/load switch | times | 10000 | 10000 | 10000 | ||||
| Disconnector/grounding switch | 3000 | 3000 | 3000 | ||||||