12kv Dry Air Insulated Environmentally friendly RMU switchgear for Indoor
Since the 1990s, with accelerating urbanization and continual improvement of power supply reliability, overhead lines have been replaced by buried cables and indoor switching stations by outdoor switching stations. The small, touchable, all-insulated, flood-control, and maintenance-free ring main units have rapidly developed and are widely used in various locations requiring reliable power distribution systems, including urban commercial centers, industrial districts, airports, electrified railways, and expressways. These units can be used singly indoors or outdoors, as well as integrated into prefabricated substations.
The MKE series solid-insulated ring main units incorporate advanced production facilities and manufacturing technology, enabling localized production that significantly reduces manufacturing costs and shortens delivery periods. This product line has received favorable responses since its launch.
Key Specifications
- Product Model: MKE-12
Rated Specification: 12 kV – 630 A
Altitude: ≤ 1000 m (higher-altitude version available on request)
Panel-Extension Options: Side extension / Top extension
Operation Mode: Manual or Electric
Integral Disconnector: With or Without
Control Voltage: 24 V, 48 V, 220 V (110 V available on request)
Standard Configuration: Vacuum circuit-breaker , Three-position disconnector / earthing switch
Technical Specifications
| Item |
Unit |
circuit breaker cell |
disconnector cell |
| Rated voltage |
kV |
12 |
12 |
| Rated current |
A |
630 |
630 |
| Rated frequency |
Hz |
50 |
50 |
| Rated insulation level |
1 min power frequency withstand voltage (phase to phase & phase to ground) |
kV |
42 |
42 |
| 1min Power Frequency Withstand Voltage (lsolation Gap) |
48 |
48 |
| RatedPower Frequency Withstand Voltage(Control &Auxiliary Circuits) |
2 |
2 |
| Lightning Impulse Withstand Voltage(Phase-to-Phase &Phase-to-Ground) |
75 |
75 |
| Lightning Impulse Withstand Voltage (lsolation Gap) |
85 |
85 |
| |
|
|
| Short-Circuit Breaking Current |
kA |
20 |
/ |
| Rated Short-Circuit Making Current |
kA |
50 |
/ |
| Rated Short-Time Withstand Current |
kA |
20 |
20 |
| Rated Short-Time Duration |
s |
4 |
4 |
| Rated Peak Withstand Current |
kA |
50 |
50 |
| Rated transfer current |
A |
/ |
/ |
| Rated Operating sequence |
/ |
O-0.3s-CO-180s-CO |
| Mechanical life |
times |
10000 |
3000/5000 |