| Parameter | Specification |
|---|---|
| Specification | BTLY 0.6/1kV 5*16mm² |
| Rated Voltage | 0.6/1kV |
| Conductor | Flexible Stranded Copper |
| Insulation | Mineral Composite / PVC |
| Sheath | LSZH (Low Smoke Zero Halogen) |
| Core Structure | 5 Core (equal 16mm² cores) |
| Fire Resistance | ≥90 min at 750~950°C (IEC 60331 / BS 6387 CWZ) |
| Rated Current | ~76A (air installation, 25°C ambient temperature) |
| Working Temp. | 90°C normal / 250°C fire |
| Compliance Standards | GB/T 34926 / IEC 60331 / GB/T 12706 / BS 6387 |
Ensures continuous power supply for at least 90 minutes under flame exposure, critical for evacuation and fire systems.
Unlike traditional rigid mineral cables, BTLY supports easier installation with bending capability suitable for complex routes.
Emits minimal toxic gases, protecting life and sensitive electronics in enclosed environments.
Stable insulation resistance, low capacitance, and durable structure under harsh operating conditions.
Ideal for smoke control systems, fire pumps, elevator supply, and tunnel lighting.