XLPE insulated power cable featuring high mechanical strength, strong resistance to environmental stress, excellent electrical performance, strong compressive ability, and chemical corrosion resistance. Suitable for transmission and distribution systems with rated voltage of 0.6/1kV.
Operating Standards: GB/T 12706, IEC 60502 and related domestic and foreign standards including BS, VDE, JIS, AEIC.
Temperature Ratings: Maximum allowable working temperature of cable conductor: 90°C under normal conditions, 250°C under short-circuit conditions (maximum short-circuit duration: 5s).
| No. of cores × section (mm²) | Normal insulation thickness (mm) | Normal thickness of oversheath | Approximate overall diameter of cable (mm) | Approximate weight of cable (kg/km) |
|---|---|---|---|---|
| 4×4 | 0.7 | 1.8 | 12.5 | 282 |
| 4×6 | 0.7 | 1.8 | 14.7 | 383 |
| 4×10 | 0.7 | 1.8 | 16.9 | 565 |
| 4×16 | 0.7 | 1.8 | 19.3 | 783 |
| 4×25 | 0.9 | 1.8 | 23.5 | 1241 |
| 4×35 | 0.9 | 1.8 | 26.7 | 1631 |
| 4×50 | 1.0 | 1.8 | 28.0 | 2080 |
| 4×70 | 1.1 | 2.0 | 33.2 | 2952 |
| 4×95 | 1.1 | 2.1 | 38.0 | 3970 |
| 4×120 | 1.2 | 2.3 | 40.9 | 4894 |
| 4×150 | 1.4 | 2.4 | 46.0 | 5980 |
| 4×185 | 1.6 | 2.6 | 52.5 | 7442 |
| 4×240 | 1.7 | 2.8 | 59.4 | 9764 |
| 4×300 | 1.8 | 3.0 | 66.2 | 12122 |
| 4×400 | 2.0 | 3.3 | 73.8 | 15624 |
| 4×500 | 2.2 | 3.5 | 89.3 | 19877 |
| 4×630 | 2.4 | 3.8 | 99.6 | 25124 |