U-1000 RO2V/R2V 0.6/1 kV XLPE Insulation PVC Sheath Power Cable designed for reliable electricity supply in low voltage installation systems.
Used for electricity supply in low voltage installation systems. Suitable for installation in indoors and outdoors, in cable ducts, underground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
| Number of conductor and size | Insulation thickness (mm) | Outer sheath thickness (mm) | Outer diameter approx. (mm) | Weight of cable approx. (kg/km) | Permissible current rating in open air (A) | Permissible current rating when buried (A) |
|---|---|---|---|---|---|---|
| 1 x 1.5mm² | 0.7 | 1.4 | 5.6 | 45 | 24 | 34 |
| 1 x 2.5mm² | 0.7 | 1.4 | 6.0 | 57 | 33 | 46 |
| 1 x 4mm² | 0.7 | 1.4 | 6.5 | 75 | 45 | 59 |
| 1 x 6mm² | 0.7 | 1.4 | 7.0 | 97 | 58 | 74 |
| 1 x 10mm² | 0.7 | 1.4 | 8.3 | 147 | 80 | 101 |
| 1 x 16mm² | 0.7 | 1.4 | 9.5 | 215 | 107 | 128 |
| 1 x 25mm² | 0.9 | 1.4 | 11.0 | 310 | 138 | 144 |
| 1 x 35mm² | 0.9 | 1.4 | 12.0 | 410 | 169 | 174 |
| 1 x 50mm² | 1.0 | 1.4 | 13.5 | 540 | 207 | 206 |
| 1 x 70mm² | 1.1 | 1.4 | 15.5 | 745 | 268 | 254 |
| 1 x 95mm² | 1.1 | 1.5 | 17.5 | 1010 | 328 | 301 |
| 1 x 120mm² | 1.2 | 1.5 | 19.0 | 1250 | 382 | 343 |
| 1 x 150mm² | 1.4 | 1.6 | 21.0 | 1535 | 441 | 387 |
| 1 x 185mm² | 1.6 | 1.6 | 23.5 | 1910 | 506 | 434 |
| 1 x 240mm² | 1.7 | 1.7 | 26.0 | 2470 | 599 | 501 |
| 1 x 300mm² | 1.8 | 1.8 | 28.5 | 3080 | 693 | 565 |
| 1 x 400mm² | 2.0 | 1.9 | 32.0 | 3995 | 825 | 662 |
| 1 x 500mm² | 2.2 | 2.0 | 35.0 | 4901 | 946 | 750 |
| 1 x 630mm² | 2.4 | 2.2 | 40 | 6168 | 1088 | 851 |