SF6 switch is a high-voltage appliance widely used in power system, and the reliable operation of SF6 switch has become one of the most concerned issues in the power supply department. SF6 gas density relay is an important component used to monitor SF6 gas density change in SF6 switch body during operation, its performance directly affects the safety of SF6 switch operation. SF6 gas density relay running in the field because of infrequent action, after a period of time often appear inflexibility, poor contact contact and other phenomena, and some will appear density relay temperature compensation performance deteriorates, when the ambient temperature sudden change often lead to SF6 density relay misoperation. Therefore, DL/T596 "Preventive Test Procedures for Power Equipment" stipulates that each SF6 switch user should regularly verify SF6 gas density relays. From the actual operation situation, the SF6 density relay and pressure gauge in the field operation are also very necessary for regular calibration
| Parameter | Specification |
|---|---|
| Power Supply | Lithium battery or AC220V/50Hz |
| Power Consumption | 4W |
| Accuracy Level | 0.2 level |
| Pressure Display Resolution | 0.0001 MPa |
| Pressure Calibration Range | 0 ~ 1.0 MPa |
| Contact Resistance Range | 0 ~ 25 Ω |
| Resistance Measurement Accuracy | ±5%FS |
| Resistance Display Resolution | 1 mΩ |
| Temperature Measurement Range | -50°C ~ 150°C |
| Temperature Measurement Accuracy | ±0.5°C |
| Temperature Display Resolution | 0.1°C |
| Verification Object | Single alarm/block/overpressure, any combination of alarm + block + overpressure |
| Pressure Type | Absolute pressure, relative pressure |
| Display | 800×600 graphic color LCD screen |
| Operation Mode | Resistive touch screen |
| Printer | High-speed thermal micro printer |
| Printing Format | Chinese character report type printing |
| Storage Capacity | Up to 150 test results |
| Dimensions | Main unit: 380mm×320mm×180mm Accessory box: 465mm×370mm×145mm |
| SF6 Gas Density Display | Pressure at measured environment, equivalent pressure at 20°C |
| Weight | 2.5 kg |
![SF6 Density Relay Chec SF6 Density Meter Check 0.2 Level [KS2001]](https://img.machineu.com/nimg/75/1d/89ed30867122e6f588a910a092c2.jpg)
![SF6 Density Relay Chec SF6 Density Meter Check 0.2 Level [KS2001]](https://img.machineu.com/nimg/4f/c4/68862645cdecad22d0353e979b44.jpg)
![SF6 Density Relay Chec SF6 Density Meter Check 0.2 Level [KS2001]](https://img.machineu.com/nimg/f4/ef/7797d21058cab5dcfbd734d8c106.jpg)
![SF6 Density Relay Chec SF6 Density Meter Check 0.2 Level [KS2001]](https://img.machineu.com/nimg/2f/c8/089c8a827e87bdda1c91181ffeac.jpg)
![SF6 Density Relay Chec SF6 Density Meter Check 0.2 Level [KS2001]](https://img.machineu.com/nimg/e4/09/be332b685090c281a73be504119c.jpg)
1 host
1 power cord
1 high-pressure steel cylinder
One intake pipe (250cm)
Measure 1 trachea (250cm)
One vent pipe (80cm)
Transition joint (serial numbers ○ 1- ○ 14) 1 set
Inflatable adapter (serial number ○ 15) 1 piece
Public connector (serial number ○ 16) 1 piece
16-core test wire
2 rolls of printing paper
2 rolls of raw material tape
2 2A insurance tubes
1 manual
Top-tier Technical AuthorityStandard-setting enterprise | 0.01ppm precision SF6 leak detector | Multiple patents & certifications
One-stop SF6 Solution RangePortable detectors to recovery systems | 100% accredited by national labs
Customizable Turnkey ServicesTailored equipment design | On-site installation & debugging
Global Support & Proven Reputation1000+ global clients | Localized after-sales service
Eco-compliant & Cost-efficientAligns with EU F-gas Directive | Zero-emission SF6 handling