The LF-03-FR SF6 Gas Leak Detector represents an advanced portable solution engineered to accurately identify SF6 leaks in high-voltage equipment including GIS, circuit breakers, and switches. Equipped with an imported NDIR infrared sensor and sophisticated calibration technology, this detector is capable of identifying leaks as low as 0.1ppm with an accuracy of ≤±2% F.S., and it provides results within 1 seconds.
This detector is an ideal choice for power utilities, maintenance teams, and manufacturing enterprises. Place an order now to enhance the speed and precision of your SF6 leak detection capabilities!
| Technical Parameters | Details |
|---|---|
| Operating Voltage | Lithium battery or AC220V/50Hz |
| Detection Principle | NDIR non-dispersive infrared (double-beam) |
| Measuring Range | 0-1000 PPM (customizable range available) |
| Detection Accuracy | ≤±2% F.S. (relative to the specified measuring range) |
| Minimum Detection Limit | 0.1 ppm |
| Highest Sensitivity | 0.1 ppm |
| Resolution | 0.1 ppm |
| Response Time | ≤1S (response available) |
| Preheating Time | ≤3 min |
| Detection Method | Handheld suction type |
| Operating Humidity | ≤90% RH |
| Display Mode | - Main screen: 800*480 graphic color LCD - Handle: 320*240 color LCD |
| Operation Mode | Resistive touch screen |
When you turn on the power switch on the panel, the instrument will enter the boot screen. Once the initialization process is complete, the main interface will be displayed, as shown in the following figure. This interface includes functions such as "SF6 Quantitative Leakage Detection", "Zero Calibration", "Cover Algorithm", "Settings", and "Device Information".