1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Terminal blocks with test sockets, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC
Technical Data
|   			 General specifications  |   		||
|---|---|---|
|   			 Signal type  |   			  			 Analog input  |   		|
|   			 Functional safety related parameters  |   		||
|   			 Safety Integrity Level (SIL)  |   			  			 SIL 2  |   		|
|   			 Systematic capability (SC)  |   			  			 SC 3  |   		|
|   			 Supply  |   		||
|   			 Connection  |   			  			 Power Rail or terminals 9+, 10-  |   		|
|   			 Rated voltage  |   			  			 19 ... 30 V DC  |   		|
|   			 Ripple  |   			  			 within the supply tolerance  |   		|
|   			 Power dissipation  |   			  			 approx. 1.4 W at 20 mA transfer current, 250 Ω in both outputs  |   		|
|   			 Power consumption  |   			  			 2 W  |   		|
|   			 Input  |   		||
|   			 Connection side  |   			  			 field side  |   		|
|   			 Connection  |   			  			 terminals 1+, 2- (sink); 3+, 4- (source)  |   		|
|   			 Input signal  |   			  			 0/4 ... 20 mA  |   		|
|   			 Voltage drop  |   			  			 terminals 3, 4: ≤ 6.1 V at 20 mA  |   		|
|   			 Short-circuit current  |   			  			 terminals 1+, 2-: 25 mA  |   		|
|   			 Input resistance  |   			  			 terminals 1+, 2-: max. 500 Ω (BRAIN)  |   		|
|   			 Available voltage  |   			  			 terminals 1+, 2-: ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA  |   		|
|   			 Output  |   		||
|   			 Connection side  |   			  			 control side  |   		|
|   			 Connection  |   			  			 source: terminals 5-, 6+; 7-, 8+  |   		|
|   			 Load  |   			  			 channel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)  |   		|
|   			 Output signal  |   			  			 0/4 ... 20 mA or 0/1 ... 5 V  |   		|
|   			 Ripple  |   			  			 max. 50 µA rms  |   		|
|   			 Transfer characteristics  |   		||
|   			 Deviation  |   			  			 Iout < 20 µA (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V  |   		|
|   			 
  |   			  			 Influence of ambient temperature  |   			  			 current output: 0.25 µA/K  |   		
|   			 Frequency range  |   			  			 field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB)  |   		|
|   			 Settling time  |   			  			 6 ms  |   		|
|   			 Rise time/fall time  |   			  			 2 ms  |   		|
|   			 Galvanic isolation  |   		||
|   			 Output/power supply  |   			  			 functional insulation, rated insulation voltage 50 V AC  |   		|
|   			 Output/Output  |   			  			 functional insulation, rated insulation voltage 50 V AC  |   		|
|   			 Indicators/settings  |   		||
|   			 Display elements  |   			  			 LED  |   		|
|   			 Control elements  |   			  			 DIP switch  |   		|
|   			 Configuration  |   			  			 via DIP switches  |   		|
|   			 Labeling  |   			  			 space for labeling at the front  |   		|
|   			 Directive conformity  |   		||
|   			 Electromagnetic compatibility  |   			  			 
  |   		|
|   			 
  |   			  			 Directive 2014/30/EU  |   			  			 EN 61326-1:2013 (industrial locations)  |   		
|   			 Conformity  |   		||
|   			 Electromagnetic compatibility  |   			  			 NE 21:2012  |   		|
|   			 Degree of protection  |   			  			 IEC 60529:2001  |   		|
|   			 Protection against electrical shock  |   			  			 UL 61010-1:2012  |   		|
|   			 Ambient conditions  |   		||
|   			 Ambient temperature  |   			  			 -20 ... 60 °C (-4 ... 140 °F)  |   		|
|   			 Mechanical specifications  |   		||
|   			 Degree of protection  |   			  			 IP20  |   		|
|   			 Connection  |   			  			 screw terminals  |   		|
|   			 Mass  |   			  			 approx. 100 g  |   		|
|   			 Dimensions  |   			  			 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2  |   		|
|   			 
  |   			  			 Height  |   			  			 124 mm  |   		
|   			 
  |   			  			 Width  |   			  			 12.5 mm  |   		
|   			 
  |   			  			 Depth  |   			  			 114 mm  |   		
|   			 Mounting  |   			  			 on 35 mm DIN mounting rail acc. to EN 60715:2001  |   		|
|   			 Data for application in connection with hazardous areas  |   		||
|   			 EU-type examination certificate  |   			  			 BASEEFA 13 ATEX 0077 X  |   		|
|   			 
  |   			  			 Marking  |   			  			 
  |   		
|   			 
  |   			  			 Input  |   			  			 [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I  |   		
|   			 Supply  |   			  			 
  |   		|
|   			 
  |   			  			 Maximum safe voltage  |   			  			 250 V (Attention! The rated voltage can be lower.)  |   		
|   			 Equipment  |   			  			 terminals 1+, 2-  |   		|
|   			 
  |   			  			 Voltage  |   			  			 25.2 V  |   		
|   			 
  |   			  			 Voltage  |   			  			 28.2 V  |   		
|   			 
  |   			  			 Current  |   			  			 93 mA  |   		
|   			 
  |   			  			 Power  |   			  			 656 mW  |   		
|   			 
  |   			  			 Internal capacitance  |   			  			 10 nF  |   		
|   			 
  |   			  			 Internal inductance  |   			  			 0 mH  |   		
|   			 Equipment  |   			  			 terminals 3+, 4-  |   		|
|   			 
  |   			  			 Voltage  |   			  			 30 V  |   		
|   			 
  |   			  			 Current  |   			  			 115 mA  |   		
|   			 
  |   			  			 Power  |   			  			 700 mW  |   		
|   			 
  |   			  			 Voltage  |   			  			 5 V  |   		
|   			 
  |   			  			 Current  |   			  			 6.8 mA  |   		
|   			 
  |   			  			 Power  |   			  			 1.6 mW  |   		
|   			 Output  |   			  			 
  |   		|
|   			 
  |   			  			 Maximum safe voltage  |   			  			 250 V (Attention! The rated voltage can be lower.)  |   		
|   			 Certificate  |   			  			 BASEEFA 13 ATEX 0078 X  |   		|
|   			 
  |   			  			 Marking  |   			  			 
  |   		
|   			 Galvanic isolation  |   			  			 
  |   		|
|   			 
  |   			  			 Input/Output  |   			  			 safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V  |   		
|   			 
  |   			  			 Input/power supply  |   			  			 safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V  |   		
|   			 Directive conformity  |   			  			 
  |   		|
|   			 
  |   			  			 Directive 2014/34/EU  |   			  			 EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010  |   		
|   			 International approvals  |   		||
|   			 UL approval  |   			  			 
  |   		|
|   			 
  |   			  			 Control drawing  |   			  			 116-0380 (cULus)  |   		
|   			 IECEx approval  |   			  			 
  |   		|
|   			 
  |   			  			 IECEx certificate  |   			  			 IECEx BAS 13.0043X  |   		
|   			 
  |   			  			 IECEx marking  |   			  			 [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I  |   		
Related Part Number:
|   			 KCD2-SCD-EX1  |   		
|   			 KCD2-STC-EX1.20  |   		
|   			 KFD2-SR2-Ex1.W.LB  |   		
|   			 KFD2-SR2-2.W.SM  |   		
|   			 KFD2-SR2-Ex2.W.SM  |   		
|   			 KFD2-SR2-Ex2.2S  |   		
|   			 KFD2-SR2-2.2S  |   		
|   			 KFA6-DWB-EX1.D  |   		
|   			 KFA6-SR2-Ex2.W  |   		
|   			 KFA6-SR-2.3L.FA  |   		
|   			 KFA6-ER-1.5  |   		
|   			 KFA6-ER-1.W.LB  |   		
|   			 KFA6-ER-2.W.LB  |   		
|   			 KFA6-SR-2.3L.FA  |   		
|   			 KFA6-STR-1.24.4  |   		
|   			 KFD0-CS-Ex1.50P  |   		
|   			 KFD2-SH-Ex1.T.OP  |   		
|   			 KFD2-SL2-EX2.B  |   		
|   			 KFD2-SR2-EX1.W  |   		
|   			 KFD2-SR2-Ex2.W  |   		
|   			 KFD2-STC5-1.2O  |   		
|   			 KFD2-STC5-Ex1  |   		
|   			 KFD2-STC5-Ex1.H  |   		
|   			 HIC2031  |   		