1-channel isolated barrier, 24 V DC supply (Power Rail), Current input 0 mA ... 20 mA, Current output 0 mA ... 20 mA, Accuracy 0.1 %, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the field, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 35 V DC, Signal: 1 x 0 ... 20 mA, Signal [2]: 1 x 4 ... 20 mA, Field device: 1 x I/P converters, Field device [2]: 1 x positioner, Signal: 1 x 0 ... 20 mA
Technical Data
|   			 General specifications  |   		||
|---|---|---|
|   			 Signal type  |   			  			 Analog output  |   		|
|   			 Functional safety related parameters  |   		||
|   			 Safety Integrity Level (SIL)  |   			  			 SIL 2  |   		|
|   			 Supply  |   		||
|   			 Connection  |   			  			 Power Rail or terminals 7+, 8-  |   		|
|   			 Rated voltage  |   			  			 20 ... 35 V DC  |   		|
|   			 Ripple  |   			  			 within the supply tolerance  |   		|
|   			 Rated current  |   			  			 max. 50 mA  |   		|
|   			 Power dissipation  |   			  			 1.4 W  |   		|
|   			 Input  |   		||
|   			 Connection side  |   			  			 control side  |   		|
|   			 Connection  |   			  			 terminals 9+, 10-, 11+  |   		|
|   			 Voltage drop  |   			  			 approx. 4 V at 20 mA  |   		|
|   			 Input current  |   			  			 ≤ 100 µA up to 50 °C (122 °F) at 10 V  |   		|
|   			 Limit  |   			  			 max. 40 mA  |   		|
|   			 Transmission range  |   			  			 0 ... 20 mA  |   		|
|   			 Output  |   		||
|   			 Connection side  |   			  			 field side  |   		|
|   			 Connection  |   			  			 terminals 1+, 2-  |   		|
|   			 Voltage  |   			  			 17 V at 20 mA  |   		|
|   			 Current  |   			  			 0 ... 20 mA  |   		|
|   			 Load  |   			  			 output resistance: max. 3 Ω  |   		|
|   			 Transfer characteristics  |   		||
|   			 Deviation  |   			  			 at 20 °C (68 °F), 4 ... 20 mA  |   		|
|   			 
  |   			  			 Influence of ambient temperature  |   			  			 ≤ ± 0.01 %/K  |   		
|   			 Rise time  |   			  			 < 10 ms  |   		|
|   			 Galvanic isolation  |   		||
|   			 Input/power supply  |   			  			 functional insulation, rated insulation voltage 50 V AC  |   		|
|   			 Indicators/settings  |   		||
|   			 Display elements  |   			  			 LED  |   		|
|   			 Labeling  |   			  			 space for labeling at the front  |   		|
|   			 Directive conformity  |   		||
|   			 Electromagnetic compatibility  |   			  			 
  |   		|
|   			 
  |   			  			 Directive 2014/30/EU  |   			  			 EN 61326-1:2013 (industrial locations)  |   		
|   			 Conformity  |   		||
|   			 Degree of protection  |   			  			 IEC 60529:2001  |   		|
|   			 Protection against electrical shock  |   			  			 UL 61010-1:2012  |   		|
|   			 Ambient conditions  |   		||
|   			 Ambient temperature  |   			  			 -20 ... 60 °C (-4 ... 140 °F)  |   		|
|   			 Mechanical specifications  |   		||
|   			 Degree of protection  |   			  			 IP20  |   		|
|   			 Connection  |   			  			 screw terminals  |   		|
|   			 Mass  |   			  			 approx. 100 g  |   		|
|   			 Dimensions  |   			  			 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1  |   		|
|   			 
  |   			  			 Height  |   			  			 107 mm  |   		
|   			 
  |   			  			 Width  |   			  			 20 mm  |   		
|   			 
  |   			  			 Depth  |   			  			 115 mm  |   		
|   			 Mounting  |   			  			 on 35 mm DIN mounting rail acc. to EN 60715:2001  |   		|
|   			 Data for application in connection with hazardous areas  |   		||
|   			 EU-type examination certificate  |   			  			 BAS 02 ATEX 7203 X  |   		|
|   			 
  |   			  			 Marking  |   			  			 
  |   		
|   			 Certificate  |   			  			 TÜV 99 ATEX 1499 X  |   		|
|   			 
  |   			  			 Marking  |   			  			 
  |   		
|   			 Directive conformity  |   			  			 
  |   		|
|   			 
  |   			  			 Directive 2014/34/EU  |   			  			 EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010  |   		
|   			 International approvals  |   		||
|   			 FM approval  |   			  			 
  |   		|
|   			 
  |   			  			 Control drawing  |   			  			 116-0440  |   		
|   			 UL approval  |   			  			 
  |   		|
|   			 
  |   			  			 Control drawing  |   			  			 116-0441 (cULus)  |   		
|   			 IECEx approval  |   			  			 
  |   		|
|   			 
  |   			  			 IECEx certificate  |   			  			 IECEx BAS 05.0041X  |   		
|   			 
  |   			  			 IECEx marking  |   			  			 [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I  |   		
Related Models:
|   			 KFU8-UFT  |   			  			 KFD0-CS-Ex1.51P  |   		
|   			 K-HM26-2M-261533  |   			  			 KFD0-CS-Ex2.50P  |   		
|   			 NBB15-U1-E2  |   			  			 KFD0-CS-Ex2.51P  |   		
|   			 NBB1,5-5GM25-E2  |   			  			 KFD0-RO-Ex2  |   		
|   			 NBB1,5-5GM25-E2-V3  |   			  			 KFD0-SCS-Ex1.55  |   		
|   			 NBB1,5-F79-E0  |   			  			 KFD0-SD2-Ex2.1045  |   		
|   			 NBB1,5-F79-E2  |   			  			 KFD0-SD2-Ex2.1245  |   		
|   			 NBB15-U1-Z2  |   			  			 KFD0-TR-Ex1  |   		
|   			 NBB5-18GM50-E2-V1  |   			  			 KFD0-CC-1  |   		
|   			 NBB15-30GM30-E2-V1  |   			  			 KFD0-HMS-16  |   		
|   			 NBB15-30GM50-A2-V1  |   			  			 KFD0-RSH-1.4S.PS2  |   		
|   			 NBB15-30GM50-E2  |   			  			 KFD0-SD2-EX1.10100  |   		
|   			 NBB15-30GM50-E2-M  |   			  			 KFD0-SD2-EX1.1045  |   		
|   			 NBB15-30GM50-E2-V1  |   			  			 KFD2-UT2-1  |   		
|   			 NBB15-30GM50-E2-V1-M  |   			  			 KFD2-CD-1.32  |   		
|   			 NBB8-18GM30-E2  |   			  			 KFD2-CD-EX1.32  |   		
|   			 NBB8-18GM30-E2-V1  |   			  			 KFD2-HMM-16  |   		
|   			 NBB8-18GM60-A2-V1  |   			  			 KFD2-SH-EX1.T  |   		
|   			 NJ4-12GK-SN  |   			  			 KFD2-UT2-1  |   		
|   			 NJ5-18GK-N  |   			  			 KFD2-VR4-EX1.26  |   		
|   			 NJ5-18GK-N-150  |   			  			 KFU8-UFC-1.D  |   		
|   			 NJ5-18GM-N  |   			  			 V15-G-2M  |   		
|   			 NJ8-18GK-N  |   			  			 Z 787  |   		
|   			 RD0-FB-EX4  |   			  			 Z787.H  |   		
|   			 RD0-TI-Ex8.FF.*  |   			  			 HIC2031  |   		
|   			 Z787.F  |   			  			 Z787.H.F  |   		