Power input
| Rated input voltage (V) |
Three-phase 380V (-15%) to 480V (+10%) |
| Rated input current (A) |
3.4A |
| Rated frequency (Hz) |
50Hz or 60Hz, within the allowable range of 47 to 63Hz |
Power output
| Rated motor capacity (kW) |
1.5kW (Variable Torque) |
| Rated output (kVA) |
2.6kVA |
| Rated Current (A) |
3.4A |
| Rated output voltage (V) |
0 - Input Voltage, with an error less than 5% |
| Output frequency (Hz) |
0~400Hz |
Technical control performance
| Control method |
V/F control mode, without PG sensorless vector control (SLVC) mode |
| Motor type |
Asynchronous motor only |
| Speed control range |
1:50 (V/F), 1:100 (SLVC) |
| Speed control accuracy |
±0.5% (without PG vector control) |
| Speed fluctuation |
±0.3% (without PG vector control) |
| Torque response |
<100ms (without PG vector control) |
| Torque control accuracy |
±15% |
| Starting torque |
1Hz 120% (without PG vector control) |
| Overload capacity |
120% rated current for 1 minute, allowed once every 10 minutes (Variable Torque mode) |
Operating control characteristics
| Frequency setting method |
Keyboard number setting, analog quantity setting, pulse frequency setting, multi-stage speed running setting, simple PLC setting, PID setting, MODBUS RTU/Profibus communication setting, etc. Realize the combination of settings and the switching of setting channels. |
| Automatic voltage regulation function |
When the grid voltage changes, it can automatically maintain the output voltage constant. |
| Fault protection function |
Provide comprehensive fault protection functions: overcurrent, overvoltage, undervoltage, overheating, phase loss, overload, ground fault, motor stall, etc. |
| Speed tracking restart function |
Realize the smooth and impact-free startup of a rotating motor |
| Simulated input |
2 channels, AI1: 0(2) to 10V / 0(4) to 20mA, AI2: 0 to 10V / 0(4) to 20mA |
| Simulation output |
1 channel, AO1: 0 to 10V / 0(4) to 20mA |
| Digital input |
6-channel opto-isolated general input, PNP/NPN selectable, maximum frequency 1kHz |
| Digital output |
2-channel open collector output, maximum frequency 1kHz |
| Relay output |
2-channel programmable relay outputs, contact capacity: 3A/AC250V, 1A/DC30V |
Others
| DC reactor |
Not equipped as standard, external optional |
| Installation method |
Wall-mounted installation, side-by-side installation |
| Brake unit |
No built-in brake unit, external brake unit and resistor required for braking applications |
| EMC filter |
No built-in EMC filter as standard; external C2/C3 filters available as options Optional filters: IEC61800-3 C2, IEC61800-3 C3 |
| Operating environment temperature |
-10 to 40 degrees Celsius. For use above 40 degrees Celsius, the performance will be reduced by 1% per degree up to 50°C. |
| Altitude |
Below 1000 meters, no derating required. Above 1000 meters, the rated current decreases by 1% for every 100 meters increase in altitude. |
| Protection level |
IP20 |
| Safety regulations |
Meet the requirements of CE, UL, cUL, RoHS certification |
| Cooling method |
Forced air cooling |
| Dimensions (W*H*D) |
80mm * 160mm * 120mm |
| Weight |
Approximately 1.4kg |
Note: The frequency converter should be installed in a metal distribution box that meets IP20 standards.