Holtop Dynamo Vortex Modular Air-Cooled Chilled Water (Heat Pump) Unit
The vortex module-type air-cooled chilled water (heat pump) unit utilizes advanced modular technology with air as the cooling and heating medium. This integrated central air conditioning equipment serves as both a cooling/heating source and combined unit, designed to work with fan coil units, cabinet-type, ceiling-mounted air handling units, and fresh air units to form semi-centralized air conditioning systems.
Model Specifications
| Model |
HFW-420HA1 |
HFW-560HA1 |
HFW-840HA1 |
HFW-980HA1 |
HFW-1120HA1 |
| Nominal Cooling Capacity (kW) | 420.0 | 560.0 | 840.0 | 980.0 | 1120.0 |
| Nominal Heating Capacity (kW) | 454.0 | 605.0 | 908.0 | 1059.0 | 1210.0 |
| Refrigeration Input Power (kW) | 129.2 | 172.3 | 258.4 | 301.5 | 344.6 |
| Heating Input Power (kW) | 132.4 | 176.4 | 264.8 | 308.8 | 352.8 |
| Compressor Quantity | 3 | 4 | 6 | 7 | 8 |
| Nominal Water Flow Rate (m³/h) | 72.2 | 96.3 | 144.4 | 168.5 | 192.6 |
| Dimensions L×W×H (mm) | 3540×2280×2540 | 4700×2280×2540 | 7080×2280×2540 | 8240×2280×2540 | 9400×2280×2540 |
| Weight (kg) | 4020 | 5350 | 8040 | 9370 | 10700 |
Notes:
1. Nominal cooling capacity test conditions: water flow rate 0.172 m³/(h*kW), outlet water temperature 7°C, outdoor ambient temperature 35°C.
2. Nominal heating capacity test conditions: water flow rate 0.172 m³/(h*kW), outlet water temperature 45°C, outdoor dry/wet bulb temperature 7/6°C.
3. Modular unit combination requires on-site fabrication of total water pipe (not provided by factory).
4. Units can be combined from 1 to 16 modules using same or different models.
5. Control accessories must be ordered separately and include remote controller, user manual, and connection cables.