Microcomputer Relay Protection Tester - 6 Phase Analyzer
Professional 6-phase relay protection tester with microcomputer technology, featuring comprehensive output capabilities and backed by a 2-year warranty for reliable electronic power testing applications.
Key Features & Indicators
- LED working indication: Flashing indicates waiting mode, constant illumination indicates active operation
- Communication interface: External laptop connectivity for remote instrument control
- USB 2.0 interface: Supports mouse, keyboard, U-disk, and other peripheral devices
- Switch input: Captures protection device output signals and measures timing
- Switch output: Controls external devices with passive nodes (max capacity: AC220V/1A)
- Device auxiliary power supply: Outputs DC ±110V power with maximum 2A current for protection device operation
- Dual current output terminals: IA, IB, IC, Ia, Ib, Ic with IN common terminal and LED source status indication
- Dual voltage output terminals: UA, UB, UC, Ua, Ub, Uc with UN common terminal and LED short-circuit indication
- Touchpad control: Full-direction touch control with left/right confirmation keys
- Keyboard input: For fixed value data entry
- 10.4-inch LED LCD display: High-resolution 800×600 screen for clear data visualization
Technical Specifications
AC Current Output
| Parameter |
Specification |
| Single phase current output (RMS) |
0–30A/phase, accuracy: 0.2% ± 5mA |
| Six current parallel output (RMS) |
0–180A/three phase in-phase parallel output |
| Duty Cycle |
10A |
| Maximum output power per phase |
320VA |
| Maximum output power (six phase parallel) |
1000VA |
| Maximum output time (six parallel current) |
5s |
| Frequency Range |
0–1000Hz, accuracy: 0.01Hz |
| Harmonic number |
2–20 times |
| Phase |
0–360°, accuracy: 0.1° |
DC Current Output
| Parameter |
Specification |
| DC current output |
0–±10A/phase, accuracy: 0.2% ± 5mA |
AC Voltage Output
| Parameter |
Specification |
| Single phase voltage output (RMS) |
0–125V/phase, accuracy: 0.2% ± 5mV |
| Line voltage output (RMS) |
0–250V |
| Phase/line voltage output power |
75VA/100VA |
| Frequency range |
0–1000Hz, accuracy: 0.001Hz |
| Harmonic wave |
2–20 times |
| Phase |
0–360°, accuracy: 0.1° |
DC Voltage Output
| Parameter |
Specification |
| Single phase voltage output amplitude |
0–±150V, accuracy: 0.2% ± 5mV |
| Output amplitude of line voltage |
0–±300V |
| Phase/line voltage output power |
90VA/180VA |
Switch & Timing Specifications
| Parameter |
Specification |
| Switch input terminals |
8 channels |
| Air contact |
1–20mA, 24V, internal active output |
| Potential reversal |
Passive contact: low resistance short circuit signal Active contact: 0-250V DC |
| Switch output terminals |
4 pairs, no contact, breaking capacity: 110V/2A, 220V/1A |
| Time frame |
1ms–9999s, measuring accuracy: 1ms |
Physical Specifications
| Parameter |
Specification |
| Dimensions |
390 × 395 × 180 mm |
| Weight |
Approximately 18kg |
| Power Supply |
AC125V±10%, 50Hz, 10A |
Advanced Features
- Comprehensive field testing capabilities with standard six-phase voltage and current output for traditional and modern microcomputer protection devices
- Classic intuitive operation interface with clear navigation and high-performance embedded industrial control computer.
- System recovery function prevents crashes from improper shutdown procedures
- Ultra-thin industrial keyboard and optical mouse for PC-like operation experience
- DSP+FPGA main control board with 16-bit DAC output generating 2000 high-density sine waves per week for superior waveform quality
- High-fidelity linear power amplifier ensures accuracy across current ranges
- Direct USB communication with PC without adapter cables
- Laptop connectivity option with identical software operation
- GPS synchronization testing capability for multi-location coordinated testing
- Independent DC auxiliary voltage source output: 110V (1A), 125V (0.6A)
- Software self-calibration function eliminates manual potentiometer adjustment
Product Images