Temperature-sensing, self-actuated fire extinguishing devices are an advanced class of fire suppression equipment developed both domestically and internationally. They are fixed, non-electric, and self-actuated, requiring no power source or traditional fire detection and alarm equipment. The entire system consists solely of a fire extinguishing agent storage cylinder and a flexible fire detection tube. The fire detection tube integrates fire detection, device activation, and fire extinguishing agent release. It can be conveniently positioned closest to any potential ignition source. In the event of a fire, the fire detection tube ruptures due to heat, instantly releasing the fire extinguishing agent for targeted extinguishing.
Direct CO2
Indirect CO2
The fire detection tube is connected to the fire extinguishing agent container through a container valve and fixed above the most likely fire source to detect the fire source. When a fire occurs, the fire detection tube softens and bursts at the highest temperature point. The pressure drop in the fire detection tube activates the container valve, and the fire extinguishing agent is released through the burst hole of the fire detection tube to extinguish the fire. At the same time, the alarm bell sounds, notifying the user that the fire extinguishing device has been activated and that the device needs to be confirmed, the system needs to be repaired, and the fire extinguishing agent needs to be refilled.
The temperature-sensing automatic fire extinguishing system solves the long-standing fire prevention problem in fire-prone spaces such as electrical equipment, control boxes, and distribution boards — a problem that has long plagued the fire protection industry. Currently, this system has been widely used in power plants, telecommunications, broadcasting, petrochemical, and railway systems in China, accumulating a wealth of successful experience.
2.1 Carbon dioxide-filled fire-detection tube automatic fire-extinguishing devices can be used to extinguish the following fires:
2.3 Carbon dioxide-filled fire-detection tube automatic fire-extinguishing devices must not be used to extinguish the following fires:
Main components include a container containing fire extinguishing agent, a container valve, a pressurized fire detection tube that releases the agent and has fire detection capabilities, a pressure gauge, a one-way valve, a pressure switch, an alarm, and a dedicated connector for the fire detection tube.
The fire detection tube is a high-tech non-metallic composite product. It combines long-term leak resistance, flexibility, and effective temperature sensitivity. After pressurization, it bursts within a certain temperature range to release the extinguishing agent or transmit a fire signal.
Main components include a container containing fire extinguishing agent, a container valve, a pressurized fire detection tube, a release tube, a nozzle, a pressure gauge, a one-way valve, a pressure switch, an alarm, and a dedicated connector for the fire detection tube.
| Device Type | Device Release Type | Nominal Working Pressure | Maximum Working Pressure | Operating Temperature Range | Minimum Agent per Unit Volume | Max. Fire Detection Tube Length | Max. Release Tube Length | Maximum Loading Factor |
|---|---|---|---|---|---|---|---|---|
| Carbon dioxide temperature-sensing self-starting fire extinguishing device | Direct | 5.7 MPa | 12.1 MPa | (0~49)℃ | 2.5 kg/m³ | 25 m | -- | 0.6 kg/L |
| Device Type | Model Specifications | Agent Filling Amount (kg) | Effective Protection Scope (m³) | Max. Fire Detection Tube Length (m) | Max. Release Tube Length (m) | Device Release Type |
|---|---|---|---|---|---|---|
| Carbon dioxide temperature-sensing self-starting fire extinguishing device | WZ-Q/T-EZ6-XJ60 | 6 | 2.4 | 25 | -- | Direct |
| Device Type | Device Release Type | Nominal Working Pressure | Maximum Working Pressure | Operating Temperature Range | Minimum Agent per Unit Volume | Max. Fire Detection Tube Length | Max. Release Tube Length | Maximum Loading Factor |
|---|---|---|---|---|---|---|---|---|
| Carbon dioxide temperature-sensing self-starting fire extinguishing device | Indirect | 5.7 MPa | 12.1 MPa | (0~49)℃ | 1.5 kg/m³ | 25 m | 12 m | 0.6 kg/L |
| Device Type | Model Specifications | Agent Filling Amount (kg) | Effective Protection Scope (m³) | Max. Fire Detection Tube Length (m) | Max. Release Tube Length (m) | Device Release Type |
|---|---|---|---|---|---|---|
| Carbon dioxide temperature-sensing self-starting fire extinguishing device | WZ-Q/T-EJ45-XJ60 | 45 | 30 | 25 | 12 | Indirect |