CBA-II Multi-functional Economic Circuit Breaker Analyzer CBA is designed to meet the need of onsite test the dynamic characteristics of High-Voltage Circuit Breakers.
GDGK-306A Circuit Breaker Analyzer CBA takes the ARM7 unit for core to sample, process and output; the main characteristic is that it’s operated in alt.
CBA-II Multi-functional Economic Circuit Breaker Analyzer CBA has many advantages such as intelligence, multifunctional, accurate data, strong anti-jamming, easy operation, small size, light weight ,beautiful appearance, etc;
CBA-II Multi-functional Economic Circuit Breaker Analyzer CBA can test the Circuit Breakers as follows: indoors or outdoors Circuit Breakers with less oil or more oil, vacuum Circuit Breakers, SF6 Circuit Breakers and so on.
Contacts’ closing time and opening time;
Re-closing time;
Opening or closing’s asynchronism;
Springing time or springing times;
Clearance between open contacts/gaps, over-travel, over-shoot and springback;
Speed at instant of contacts touching (separating);
Opening (Closing) max speed;
Opening (Closing) average speed;
Display and Print V-S curve;
Operating current curve;
Closing resistance measurement;
Large color screen in touch operating;
| 1 | Time | Simultaneity measure Contacts | ≤12 |
| Range | 0—6s | ||
| Resolution | 0.01ms | ||
| 2 | Travel | Range | < 250mm |
| Resolution | 0.01mm | ||
| 3 | Error | Time measurement | ±0.5% |
| Travel measurement | ±1mm | ||
| 4 | Speed | Measure range | 0—20m/s |
| 5 | Internal Power | Output Voltage | 30V—260V |
| error | 1% | ||
| Output Current | 0~10A | ||
| 6 | Power Supply | Power Supply | AC220V±10 %, 50Hz |
| Power dissipation | ≤60w | ||
| 7 | Working Environment | Ambient temperature | 0~40°C |
| Humidity | ≤90%RH | ||
| 8 | Size | Dimension | 460mm*340mm*200mm |
| Weight | 7kg |