25HP Air Source Heat Pump for 1000M2 to 1500M2 Building Area Air conditioning
Advantages
1. Mature technology: cumulative sales of thousands of units, projects throughout the country, with a total service area of nearly 6 million m2;
2, cooling and heating double circuit: each circuit double throttle, control is more accurate.
3, large-scale flat fins: extend the defrosting time interval, heat is more durable; defrosting and drainage quickly.
4, jet booster compressor: the lowest ring temperature -25 ° C, the highest water output 65 ° C.
5, original noise reduction technology: the overall noise of the unit is only 62dB (A), very suitable for district heating
Quick information
-
It is convenient and high-efficient,suitable to different enders, e.g. fan coil of AC,radiator heating,under floor heating coilIn summer, it provide water of 7℃ for cooling; in winter it provide water of 50℃
Water circulate in the system and produce heat, safe and comfortable.
- When heating, the air-source heat pump is 40% energy-saving than that of AC .
- High automation, easy operation
Parameter
| Model |
SLNC-075Ycode name.pdf |
| Compressor capacity |
25HP |
| Function |
Heating and Cooling |
| Electricity |
380V-3N-50Hz |
| Working conditions |
℃ |
-25~+45 |
| Data |
Heata |
Nominal capacity |
KW |
44.5 |
| Input power |
KW |
18.3 |
| COP |
/ |
2.4 |
| Heating IPLV(H) |
2.7 |
| Coolb |
Nominal capacity |
KW |
62 |
| Input power |
KW |
20.7 |
| COP |
/ |
3 |
| Cooling IPLV(C) |
2.7 |
| A7W35c |
KW/COP |
75.0/4.2 |
| A2W35 |
KW/COP |
62.5/3.20 |
| A-7W35 |
KW/COP |
50/2.9 |
| A-15W55 |
KW/COP |
45.5 /1.97 |
| A-20W45 |
KW/COP |
37.4/2.04 |
| Max. running currency |
A |
56 |
| Compressor quantity |
set |
2 |
| Refrigerant/charging quantity kg |
/ |
R22/15*2 |
| Air blow type |
/ |
Top |
| Water pipe diameter |
mm |
50 |
| Rating flow |
m³/h |
12.6 |
| Water side pressure loss |
kPa |
≤45 |
| Noise level |
dB(A) |
62 |
| Overall dimensions(L×W×H) |
mm |
2100×1100×2080 |
| Weight |
kg |
730 |
A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃
a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal
More About Air source heat pump
Convenient
The selling point of air energy water heaters is air, and for household products, one of the most basic needs of people is the ease of use. Therefore, convenience has become the second bright spot of air energy water heaters. Because the amount of air is not affected by indoor and outdoor, sunny and cloudy days, compared with solar water heaters, air-energy water heaters are very convenient, whether installed indoors or outdoors, even sunny days, temperatures above zero degrees Celsius, can use. In addition, after a tank of water is used, the air-energy water heater can produce a box of hot water in less than an hour, which can be used by the family around the clock.