This system monitors real-time concentrations of particulate matter and gaseous pollutants in flue gas emitted from stationary pollution sources such as boilers, industrial furnaces, incinerators, and similar equipment. It enables comprehensive supervision of production processes and emissions directly from the source.
The Continuous Emission Monitoring System (CEMS) consists of three fundamental components:
The sample gas flows through a high-temperature heated pipeline, undergoes dust removal via a two-stage filter system, and is dehumidified by a two-stage condensation system before entering the analyzer's gas chamber. The gas chamber connects to an ultraviolet differential analyzer through ultraviolet optical fibers, ensuring precise measurement of flue gas components.
| Parameter Category | Measurement | Specifications |
|---|---|---|
| Gaseous Pollutants | SO2 | (0~200) mg/m³, customizable range |
| NO | (0~200) mg/m³, customizable range | |
| NO2 | (0~200) mg/m³, customizable range | |
| O2 | (0~25)% | |
| Repetitiveness | ≤2% | |
| 24h zero drift and range drift | ≤±2% f.s. | |
| One-week zero-point drift and range drift | ≤±3% f.s. | |
| Linear error | ≤±2% f.s. | |
| Response time | ≤120s | |
| Particulate Matter | Measured range | (0.5~15) m |
| Dust concentration range | (0~10) mg/m³, customizable range | |
| Accuracy | ≤±2% f.s./24h | |
| Flue Gas Parameters | Temperature | Measuring range: (0~300) ºC, customizable |
| Pressure | Measuring range: (-10~10) kPa | |
| Velocity of flow | Measuring range: (0~40) m/s, (0~2) kPa, optional output | |
| Humidity | Measuring range: (0~40) vol% | |
| Data Acquisition & Processing | Data transmission module | 8-way analog input, 1-channel RS485 communication interface |
| IPC | 6-way RS232 communication interface, Windows operating system | |
| Operational software | Flue gas emission monitoring software monitor | |
| Power Supply | AC 220V, 50Hz, ≤7kW |