Specifications
Brand Name :
XZH TEST
Model Number :
XHSC-60Q
Certification :
CE ISO
Place of Origin :
China
MOQ :
1 unit
Payment Terms :
T/T
Supply Ability :
2000unit/year
Delivery Time :
5-8work days
Packaging Details :
wooden box
Price :
Negotiable
Customized Support :
OEM ODM
The power supply :
220V AC±10%,50Hz
Weight :
22KG
Dimensions :
30cm*46cm*50cm
Operating temperature :
-10℃~+55℃
power :
Electronic
Description

XHSC-60Q


The digital burn-through bridge integrates burn-through and intelligent bridge. The rated voltage of the burn-through mode is 60kV, and the maximum arc current is 400mA, which can quickly burn high-resistance faults into low resistance. The maximum test current of the digital bridge is 750mA, which greatly improves the fault location accuracy. It is
particularly suitable for insulation fault pre-location of high-voltage, large-section, and long-length complex cable systems,such as insulation fault location of complex high-voltage cables with GIS terminals and cross-connections, and can quickly complete the location without removing the GIS switch and short-circuit cross-connection.


Technical Parameters


Intelligent diagnosis Output voltage 0~60kV DC,negative
Maximum output current 30mA
Burn-through mode Output voltage 0~60kV DC,negative
Maximum output current 400mA
Bridge mode Interface mode Output voltage 0~4kV DC,Bipolar
Maximum output current 750mA
Positioning accuracy ±(0.1% ·L+1)m
Display screen 320*240 dot matrix LCD, visible in sunlight
Test range 1~50000m
Power supply 100V-240V,50/60Hz
Power Maximum 2kVA
Working environment temperature -10℃~+55℃
Working environment humidity ≤90%
Overall dimensions
(length x width x height)
30cm×46cm×50cm
Enclosure protection grade IP54



* Fully automatic test, one-button operation.
* Automatically diagnose the cable fault type and guide the next operation.
* Automatically detect whether the wiring is correct, and also has protective grounding detection.
* Automatic data storage function, which can easily view historical data.
* Digital power supply control mode, the output voltage and current are more stable.
* Wide range voltage input, and automatic discharge of the test product.
* Adopts a pull-rod chassis with casters, which is light and easy to carry.
* Compared with the wave reflection method, the bridge method has no blind spot, which is particularly suitable for judging short cables and fault points near the end.
* The output voltage is high and the current is large, which is particularly suitable for pre-locatinginsulation faults in high-voltage complex cable systems with long lengths and thick cross-sections.

Digital Bridge Cable Fault Locator with Digital Burn-Through Bridge for Accurate Fault Location


Digital Bridge Cable Fault Locator with Digital Burn-Through Bridge for Accurate Fault Location



Send your message to this supplier
Send Now

Digital Bridge Cable Fault Locator with Digital Burn-Through Bridge for Accurate Fault Location

Ask Latest Price
Brand Name :
XZH TEST
Model Number :
XHSC-60Q
Certification :
CE ISO
Place of Origin :
China
MOQ :
1 unit
Payment Terms :
T/T
Contact Supplier
Digital Bridge Cable Fault Locator with Digital Burn-Through Bridge for Accurate Fault Location
Digital Bridge Cable Fault Locator with Digital Burn-Through Bridge for Accurate Fault Location
Digital Bridge Cable Fault Locator with Digital Burn-Through Bridge for Accurate Fault Location

Xi'an Xu&Hui Electromechanical Technology Co., Ltd.

Verified Supplier
3 Years
Since 2013
Business Type :
Manufacturer
Total Annual :
1000000-5000000
Employee Number :
50~100
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement