Product Brief
XHBP series VF resonant test units consist of VF control power supply, excitation transformer, reactor and capacitive voltage divider. Connecting a rectifier silicon stack to the rear of the capacitive voltage divider enables DC withstand voltage testing of equipment.
Key Performance Advantages
- Same voltage & capacity reactors: smaller size, lighter weight.
- Minimal temperature rise at rated load.
- Dry epoxy casting for high mechanical strength and superior electrical insulation.
- VF control power supply: large capacity margin, strong protection, good output waveform, high stability.
- Multiple operating modes for simple operation.
- 220V/380V single-phase power input for convenient on-site power supply.
Technical Specs
- Rated output voltage: ≤500kV (AC RMS)
- Output frequency: 20~300Hz
- Resonant voltage waveform: Pure sine wave, distortion <1.0%
- Test capacity: ≤1000kVA
- Continuous working time at full power: 60min
- Quality factor: 30~90
- Frequency adjustment: Sensitivity 0.1Hz, instability <0.05%
- Working power: 380/220V±15%/50Hz±5%