Plug In Voltage Monitor DC Voltage Monitoring Relay undervoltage protection relays
 
Detailed description
Product Model: DVM-A (potentiometer adjustment)
Product Name: DC Voltage Protector
Dimensions: 50H×40W×57.5Dmm
Mounting base (optional): PF085A&SH-3
The main function:
● Overvoltage protection: The rated voltage is adjustable from +9% to +40% and the potentiometer is adjusted.
● Undervoltage protection: The rated voltage is adjustable from -16% to +16%, and the potentiometer is adjusted.
● DC12V setting range: Undervoltage 10~14V, overvoltage 13~17V.
● DC24V setting range: undervoltage 20~28V, overvoltage 26~34V.
● DC36V setting range: Undervoltage 30~42V, overvoltage 39~51V.
● DC48V setting range: Undervoltage 40~56V, overvoltage 52~68V.
● Action delay: adjustable from 0 to 15.0 seconds
Rated voltage: DC: 12V, 24V, 36V, 48V
Indicator: Normal, Action 2 Indicators
Output contacts: 1C, 5A 250VAC
Power consumption: ≤2W
Weight: 110g
Ambient temperature: -10°C~+55°C
Relative humidity: 45~85% RH
 
The voltage protection is a protective relaying method that protects the measured voltage of the device installation. The relay protection using the voltage too low or too high is called low-voltage protection and over-voltage protection. The operating voltage of the power system is an important indicator of power quality. When it deviates from the rated voltage by more than a certain limit, it may damage the stable operation of the system, affect the quantity and quality of factory products, and may also cause damage to electrical equipment.
 
♦ Features
-- DC circuit monitoring of over and undervoltage
-- Adjustable over- and undervoltage threshold 
-- Adjustable trip delay time 
-- Powered by the measuring circuit
-- 1 C/O contact
-- 2 LEDs for status indication
 
♦ Protective Functions
-- Overvoltage
-- Undervoltage
 
♦ Typical Applications
• DC cabinet • Batteries
• Electric control system
 
♦ Approvals
• CE • CCC
 
♦ Technical data
 
| Type | DVM-A | |||||||||||||||
| Measuring | DC circuit | |||||||||||||||
| Rated voltage | DC12V,DC24V,DC36V,DC48V | |||||||||||||||
| Monitoring functions | overvoltage,undervoltage | |||||||||||||||
| Voltage setting range | 
			
  | 
		|||||||||||||||
| Trip delay time | 1-15s adjustabel | |||||||||||||||
| Indicators | Normal,Trip | |||||||||||||||
| Output contacts | 2 C/O | |||||||||||||||
| Contact capacity | 5A,250VAC | |||||||||||||||
| Dimensions(H*W*D) | 50*40*57.5mm | |||||||||||||||
| Mounting | plug-in | 