Specification
| 1 | Rated Current | A | 2000 | 1250 | 1600 | 1250 | 1250 |
| 2 | Circuit resistance at lowest rated contact force | u Ω | ≤17 | ≤25 | ≤20 | ≤25 | ≤25 |
| 3 | Rated short-circuit breaking current | KA | 25 | 12.5 | 25 | 25 | 20 |
| 4 | Breaking operations of rated short circuit breaking current | Times | 30 | ||||
| 5 | Rated short-time withstand current | KA | 25 | 12.5 | 25 | 25 | 20 |
| 6 | Rated duration of short-circuit | S | 4 | ||||
| 7 | Rated peak withstand current | KA | 63 | 31.5 | 63 | 63 | 50 |
| 8 | Rated short -circuit making current | KA | 63 | 63.5 | 63 | 63 | 50 |
| 9 | Rated breaking current of single capacitor bank | A | 630 | ||||
| 10 | Rated breaking current of back -to-back capacitor bank | A | 400 | ||||
| 11 | Rated operating sequence | O-0.3-CO-180S-CO | |||||
Mechanical data
| 1 | Weight of movable parts | Kg | 1.7 |
| 2 | Closing force due to bellow and atmosphere | N | 90±40 |
| 3 | Force required to hold contacts open at full stroke | N | 180±50 |
Mechanical requirements
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Life
|