TH48D50NZ-S-2 High-Density Rectifier Module
Key Specifications
| Input Voltage |
176-264VAC/220V |
Output Current |
50A |
| Output Voltage |
40-58VDC/48V |
Power |
3 KW |
| Parallel Operation Imbalance |
±5% |
Efficiency |
≥96% |
| Voltage Regulation Accuracy |
±0.5% |
Operating Temperature |
-10℃ to +40°C |
| Cooling Method |
Forced Air Cooling |
Noise Level |
≤55dB |
| Weight |
≤1.9kg |
Dimensions (L*W*H) |
248*110.2*44.7mm |
Product Overview
The TH48D50NZ-S-2 is an ultra-high-density 1U switching power module delivering 48V/50A (3000W) output. Featuring industry-leading ≥96% efficiency and AC/DC dual input capability, this module sets new standards for performance in a compact form factor. Designed for demanding applications, it supports Modbus communication and offers exceptional deployment flexibility.
Key Advantages
- Superior Power Density: Delivers full 3000W output in a standard 1U rack space, maximizing cabinet capacity
- Ultra-High Efficiency & Low Loss: ≥96% peak efficiency minimizes energy costs with standby power under 5W
- Flexible & Robust Design: AC/DC wide-range input, programmable power levels, and comprehensive protections ensure reliable operation in diverse conditions
- Intelligent Management: Supports remote monitoring and safe hot-swap capabilities for easy system maintenance and control
Technical Specifications
| Output Current |
50A |
Maximum Power |
3000W |
| Input Voltage Range (VAC/VDC) |
176-264V |
Adjustable Output Range |
40-58VDC |
| Voltage Regulation Accuracy |
±0.5% |
Peak Efficiency |
≥96% |
| Audible Noise |
≤55dB |
Current Sharing Imbalance |
±5% |
| Storage Temperature |
-40℃ to +60℃ |
Operating Temperature |
-10℃ to +40℃ |
| Standby Power |
≤5W |
Load Rating |
Continuous 100% rated output |
Protection Features
Automatic Current Limiting: Switches to constant current operation when output reaches set limit
Linear Power Limiting: Guarantees ≥2600W output at 154V input, 1200W at 90V input
Short-Circuit Protection: Self-protects during output short-circuit, auto-restores within ~40 seconds
Overtemperature Protection: Auto-restarts approximately 5 minutes after fault clearance
Frequency Response: Normal operation across 45Hz-60Hz input frequency range
Application Scenarios
Ideal for next-generation high-density DC power systems including:
• High-capacity telecommunications and data centers (5G base stations)
• Integrated power systems in UPS and DC backup applications
• Industrial systems where space and performance are critical
• Infrastructure upgrades to increase power capacity within existing rack footprints
Product Images
Warranty: 12 months
Place of Origin: HeBei, China