Inrow Air Conditioner Application
TCMC series Column-type Air Conditioner is intended to cool the equipment in medium and large modular data centers, container data centers, and large data rooms with high thermal density.
Refrigeration Capacity
25 to 40kW
Product Features
High Efficiency and Energy Reduction
- High-efficient frequency conversion compressor, smart adjustment of cooling capacity;
- As a revolutionary new air treatment device, the EC fan introduces aviation-grade DC motor-driven non-polar speed control. The fan has precise electronic control and is rapidly responding to output demand. Its load mode is more economical and energy-saving. And its nearly 92% working efficiency, 30% higher than the normal ones, brings a notable reduction in operation cost. The fan enjoys a longer lifespan, small vibration, low noise, maintenance-free, continuous and stable operation, for operation stability of all units;
- Optimal control strategy to ensure maximum energy saving;
- Heat exchangers and ducts in CFD optimization for high efficiency and low resistance of heat and mass transfer;
- Ultra-high thermal ratio to avoid repeated loss in humidification and dehumidification;
- Efficient environmental refrigerant.
High Reliability
- Modular design to enhance space utilization and reduce maintenance space;
- Close to heat source to reduce energy consumption;
- Unique airflow organization for cold and hot aisle containment;
- 24 hours, 365 days of continuous operation;
- All accessories are subject to rigorous inspection and testing, all in stable performance;
- PTC electric heater, safe and reliable;
- Condensate pump with high and low water level control, double protection;
- Complete alarm protection and expert self-diagnosis function, in the high-strength framework for land, sea, and air transportation.
Smart Management
- 7-inch huge color LCD touchscreen;
- Human-centered design, one-click operation;
- Optional interface in Both English and Chinese;
- Unit operating mode display function (cooling, heating, dehumidification, humidification);
- Dynamic display of color images;
- Expert self-diagnosis;
- Call self-start function;
- Standard RS485 communication interface and mod-bus communication protocol;
- Up to 32 units of networked group control;
- Backup, round-tour, and cascade, to avoid competitive operation;
- Operating temperature at 40 to 45℃.
Technical Specifications
| Model |
TCMC25 |
TCMC40 |
TCMCE25 |
TCMCE40 |
| Air Supply |
Rear return air is supplied from the front, using an on-site guide plate to adjust the air direction, with air pushed horizontally from the front, left side, right side, and left-right side |
| Circulation Air Volume m³/h |
5000 |
8200 |
5000 |
8200 |
| Overall Cooling Capacity (kW) |
25 |
38.1 |
25 |
38.1 |
| Sensible Capacity (kW) |
25 |
38.1 |
25 |
38.1 |
| Type of Refrigerant |
R410A Eco-Refrigerant |
| Type of Compressor |
Full hermetic constant speed scroll compressor |
Full hermetic EC scroll compressor |
| Type of Expansion Valve |
Mechanical thermal expansion valve |
Electronic expansion valve |
| Quantity of Fan (pc) |
6 |
2 |
6 |
2 |
| Type of Fan |
Direct connect EC fan |
| Air Filter |
G4 filter |
| Power Supply |
380V/3N~/50Hz |
| Power Distribution Parameter FLA (A) (only for cold) |
23.8 |
27.9 |
23.8 |
27.9 |
| Power Distribution Parameter FLA (A) (constant temperature and humidity) |
28.3 |
37 |
28.3 |
37 |
| Optional Heating Capacity (kW) |
3 |
6 |
3 |
6 |
| Optional Humidity Capacity (kg/h) |
2 |
2 |
2 |
2 |
| Inlet Pipe for Humidifier (only for humidification) |
G1/2 |
G1/2 |
G1/2 |
G1/2 |
| Outlet Pipe for Condensate Water (mm) |
20 |
20 |
20 |
20 |
| Air Pipe for Refrigerant (mm) |
19 |
22 |
19 |
22 |
| Liquid Pipe for Refrigerant (mm) |
16 |
19 |
16 |
19 |
| Unit Weight (kg) |
310 |
400 |
290 |
380 |
| Cabinet Size W*D*H (mm) |
300*1200*2000 |
600*1200*2000 |
300*1200*2000 |
600*1200*2000 |
| Model for Corresponding Outdoor Units |
TCMC10Y1STCT-ACS42 |
TCMC15Y1STCT-ACS72 |
TCMC10Y1STCT-ACS42 |
TCMC15Y1STCT-ACS72 |
| Power Supply for Outdoor Units |
380V/3N~/50Hz |
| Fan Quantity of Outdoor Units (pc) |
1 |
2 |
1 |
2 |
| Refrigerant Pipe Port Size |
φ22/φ16 |
φ28/φ22 |
φ22/φ16 |
φ28/φ22 |
| Unit Size (L*W*H) |
1360*968*661 |
1860*1273*655 |
1360*968*661 |
1860*1273*655 |