The PMT2 Series Particulate Transmitter is designed to measure particulate levels in emissions from dust collectors. Utilizing DC-coupled electrostatic induction sensing technology, it monitors the pA current generated as particles pass near the probe. The transmitter provides a 4-20 mA signal that varies with particulate levels, offering 6 sensitivity ranges for user selection. Features include a non-stick PTFE coated probe to prevent erroneous readings from moisture and dust buildup, and remote zero calibration for reduced maintenance. It is ideal for PLC and control panel integration with a simple 2-wire installation.
| Model Example | Series | Probe Length | Process Connection | Housing Rating | Options | Media | Particle Size | Detection Range | Temperature Limits (Ambient/Process) | Pressure Limit | Output Signal | Power Requirement | Electrical Connection | Average Time |
| PMT2-05-A-U2 | PMT2 | 05" (5") | 3/4" Male NPT | UL (IS)* | ST (Standard M20) | Air and compatible gases, conductive or non-conductive particles. | 0.3 micron and above. | 5 to 5000 pA (6 selectable ranges) | -40 to 63C (-40 to 145F) / -40 to 120C (-40 to 248F) | 30 psi (2 bar) | 4-20 mA | 12-28 VDC | 2x 1/2" Female NPT | 1 to 360 sec (10 selectable) |
| PMT2-05-A2-U2 | PMT2 | 05" (5") | 3/4" Male NPT | ATEX and IECEx (IS) | M20 (Standard) | Air and compatible gases, conductive or non-conductive particles. | 0.3 micron and above. | 5 to 5000 pA (6 selectable ranges) | -40 to 63C (-40 to 145F) / -40 to 120C (-40 to 248F) | 30 psi (2 bar) | 4-20 mA | 12-28 VDC | 2x M20 | 1 to 360 sec (10 selectable) |