The CHT-WS Series wall-mounted temperature and humidity transmitter utilizes imported digital temperature and humidity sensors that have undergone precise calibration. This calibration data is stored in the internal memory. The transmitter offers digital output for both relative humidity and temperature, ensuring full interchangeability without complex calibration processes. It excels in measurement accuracy, linearity, repeatability, interchangeability, and consistency, making it suitable for environmental equipment integration, instrument integration, and general environmental testing.
Widely used in building automation, telecommunication equipment rooms, papermaking, warehousing and logistics, shopping malls, hotels, cinemas, train stations, museums, theaters, agricultural greenhouses, hospitals, meteorology, clean workshops, and other fields requiring air temperature and humidity measurement.
| Parameter | Specification |
| Temperature Range | Standard: -40~80; Other ranges customizable |
| Humidity Range | 0~100%RH (non-condensing) |
| Accuracy | 0.2 (@25); 3%RH (10%~90%) |
| Repeatability | 0.1; 0.1%RH |
| Long-term Stability | <0.04/year; <0.5%RH/year |
| Output Signal | V: Voltage signal (0~2V, 0~5V, 0~10V selectable); I: 4~20mA (current loop); R: RS485 (Modbus-RTU protocol, default address: 01) |
| Supply Voltage | 10~30V DC |
| Response Time | <1S |
| Working Environment | Temperature: -55~120; Humidity: 95%RH |
| Load Capacity | Voltage output: Output resistance 250; Current output: 600 |
The air temperature and humidity sensor can be connected to various differential input data acquisition devices, data acquisition cards, remote data acquisition modules, etc. Please refer to the wiring diagram for details.
Temperature Conversion:
Humidity Conversion:
RS485 Signal:
Standard Modbus-RTU protocol, Baud rate: 4800; Parity: None; Data bits: 8; Stop bits: 1.
To change the address (e.g., from 1 to 2), use the following command structure: Host Slave. Example: 0x01 0x06 0x07 0xD0 0x00 0x02 0x08 0x86. If the sensor receives correctly, it will return data as per the original path. If the original address is forgotten, the broadcast address 0xFF can be used (only one slave can be connected to the host). The returned address will be the original address, which can be used for address querying.
To query data (temperature, humidity) from a sensor (address 1), use the following command: Host Slave. Example: 0x01 0x03 0x00 0x00 0x00 0x02 0xC4 0x0B. If the sensor receives correctly, it will return data: Slave Host. Example: 0x01 0x03 0x04 0xFF 0xDD 0x01 0x64 0x5A 0x66. Temperature: -3.5 (negative numbers are represented in two's complement); Humidity: 35.6%RH.