| Specification | Details |
|---|---|
| CO2 Measurement Range | 0 to 2000 ppm |
| CO2 Accuracy | 30 ppm or 3% of reading, whichever is higher* |
| Power Supply Requirements | 18-30 VAC RMS, 50/60 Hz, or 18-42 VDC (polarity protected) |
| Power Consumption | Typical 0.7 W at 24V AC RMS |
| Temperature Dependence | 0.2% FS per C (0.11% per F) |
| Stability | <2% of FS over life of sensor (15 years) |
| Pressure Dependence | 0.135% of reading per mm Hg |
| Warranty | 24 months on mechanical defects; Lifetime calibration warranty (ABC Logic on) |
| Signal Update | Every 5 seconds |
| CO2 Warm-up Time | < 2 minutes (operational), 10 minutes (maximum accuracy) |
| Operating Conditions | 32F to 122F (0C to 50C), 0 to 95% RH (non-condensing) |
| Storage Conditions | -40F to 158F (-40C to 70C) |
| Flammability Classification | UL94 5VA |
| Analog Output Options | Field selectable voltage or current; Voltage only (0-10V or 0-5V); Current only (4-20 mA) |
| Analog Output Specifications | 0-5 V or 0-10 V (100 output impedance); 4-20 mA (RL maximum 500 ) |
| Digital to Analog Error | 1% |
| Dimensions (Standard Enclosure) | 3.20" (81.40 mm) height, 4.58" (116.40 mm) width, 1.01" (25.69 mm) depth |
Designed for in-duct sampling of CO2 concentrations at flow rates greater than 400 fpm. Accommodates T5100 series sensors. Features a clear cover for observation and knockouts for conduit connection. Air sampling probe is 1-inch diameter and 8-inch long. Requires sealing of wiring penetrations.
Protects T5100 series sensors in damp or wet environments (agricultural, industrial, food processing). Designed to protect from dripping or sprayed water. Features a transparent cover and four diffusion ports for CO2 entry. Knockouts for conduit connection. Sensor response time is slowed to approximately 30 minutes for a 90% step change.
Rugged, weatherproof enclosure for T5100 series sensors in outdoor or sub-freezing environments. Ideal for monitoring outside air or CO2 in parking garages, tunnels, and loading docks. Features a temperature control circuit and internal heaters to maintain the sensor within its operating range down to -20F (-29C). Four diffusion ports for CO2 entry. Sensor response time is slowed to approximately 30 minutes for a 90% step change. Power consumption: 24V, 1.5 Amp (max).
Allows modification of standard T5100 series settings, including altitude adjustment, analog output adjustment, single point and span gas calibration, ABC Logic enable/disable, and CO2 graphing/logging. Supplied with a USB cable and software CD (T2090 UIP software kit).