KFD2-DWB-Ex1.D P+F Rotation Speed Monitor Parter Number:231203
This isolated barrier is used for intrinsic safety applications. It monitors for an overspeed or underspeed condition of a digital signal (NAMUR sensor/ mechanical contact) from a hazardous area by comparing the input frequency to the user programmed reference frequency. An overspeed or underspeed condition is signaled via the relay outputs. Line fault detection of the field circuit is indicated by a red LED, Power Rail and relay. The start-up override feature sets relay outputs to default conditions programmed by the user for up to 1,000 seconds. The unit is easily programmed by the use of a keypad located on the front of the unit. A unique collective error messaging feature is available when used with the Power Rail system.
Technical Data
|
General specifications
|
|
|
Signal type
|
Digital Input
|
Functional safety related parameters
|
|
|
Safety Integrity Level (SIL)
|
SIL 2
|
|
Supply
|
|
|
Connection
|
terminals 23+, 24- or power feed module/Power Rail
|
|
Rated voltage
|
20 ... 30 V DC
|
|
Rated current
|
approx. 100 mA
|
|
Power dissipation/power consumption
|
≤ 1.8 W / 1.8 W
|
|
Input
|
|
|
|
field side
|
|
|
Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
|