High Voltage AC Resonant Test System for Cable, Transformer, and GIS AC Withstanding Voltage Test
|
Compact & Portable Design: This voltage withstand test system features a compact footprint, lightweight construction, and high portability for easy field deployment.
On-Site Maneuverability: Designed for practical field handling, individual modules are kept under 30 kg for single-person movement, with total system weight under 60 kg for convenient two-person transport.
Flexible Power Supply: Compatible with standard 220V single-phase or 380V single-phase AC power, facilitating easy connection to common on-site power sources.
Robust Dry-Type Reactor: The reactor utilizes a dry-type, epoxy resin cast design, offering an aesthetically sealed structure, high reliability, and suitability for testing various cable types.
Low Harmonic Technology: Incorporates proprietary low-harmonic technology, maintaining total harmonic distortion below 5% (exceeding international standards) to protect primary transformers, generators, and other equipment from high-voltage harmonic damage.
Real-Time Peak Monitoring: Features standard-compliant real-time peak value monitoring, enabling continuous observation and analysis of the high-voltage test waveform.
User-Friendly Interface: Equipped with a large, clear LED screen for intuitive operation and straightforward data visualization.
Integrated Data Output: Includes a built-in micro printer for immediate printing and local saving of test reports and data at any time.
|
Common Configuration:
|
|||||
|
Model
|
Test Object
|
Main Configurations:
|
|||
|
AC power source
|
Exciting Transformer
|
Reactor
|
Capacitive Voltage Divider
|
||
|
SXBP-27/54/108-108
Test Frequency: 20~300Hz |
31500kVA/35KV Power Transformer
|
10KW 1 unit
|
10KW 1 unit
|
27KV/1A
4 Units Frequency: 20-300Hz |
120KV
|
|
35KV circuit breaker, busbar, insulator
|
|||||
|
10KV(300mm2) cable 2000m
|
|||||
|
35KV(300mm2) cable 500m
|
|||||
|
SXBP-54/108/216-216
Test Frequency: 20~300Hz |
110KV Circuit breaker and busbar
|
15KW 1 unit
|
15KW 1 unit
|
65KV/2A
4 Units Frequency: 20-300Hz |
300KV
|
|
110KV GIS ≤ 10 intervals
|
|||||
|
35KV (300mm2) cable 1500m
|
|||||
|
10KV (300mm2) cable 3000m
|
|||||
|
110KV Full Insulated Transformer
|
|||||
|
SXBP-65/130/260-520
Test Frequency: 20~300Hz |
110KV Circuit Breaker and busbar
|
30KW 1 Unit
|
30KW 1 Unit
|
45KV/1A
6 Units Frequency: 20-300Hz |
200KV
|
|
110KV GIS ≤ 10 intervals
|
|||||
|
110KV (300mm2) cable 800m
|
|||||
|
35KV (300mm2) cable 3000m
|
|||||
|
10KV(300mm2) cable 200m
|
|||||
|
110KV Full Insulated Transformer
|
|||||
|
SXBP-45/90/135/180/270-270
Test Frequency: 20~300Hz |
110KV Insulator, switchgear, GIS and etc.
|
20KW 1 unit
|
20KW 1 unit
|
45KV/1A Six Units
Frequency: 20-300Hz |
200KV
|
|
50MW/110KV Full Insulated Transformer
|
|||||
|
110KV (300mm2) cable 200m
|
|||||
|
35KV Power Transformer, switchgear, CT/PT, cable, and etc.
|
|||||
|
20MW hydrogenerator
|
|||||
|
10KV power transformer, switchgear, CT/PT, cables and etc.
|
|||||
|
SXBP18/36/54
Test Frequency: 20~300Hz |
10KV (300mm2) cable 2000m
|
5KW 1 Unit
|
5KW 1 Unit
|
27KV/1A 2 units or
18KV/1A 3 units Frequency: 20-300Hz |
60KV
|
|
35KV (300mm2) cable 500m
|
|||||
|
10KV power transformer, switchgear, CT/PT and etc.
|