Advanced HV Resonant Test System Mobile Variable Frequency HV AC Resonant Test System For Transformers, Cables and Switchgears Test
|
Uncompromised Waveform Purity: A hallmark of the resonant principle, our system outputs a sine wave with Total Harmonic Distortion (THD) ≤ 1%. This protects sensitive equipment from harmonic stress and ensures test compliance with international standards.
High Efficiency & Portability: With a Quality Factor (Q) ≥ 30, the system draws minimal input power from a standard 220V/380V single-phase source to produce high kVA output. This translates directly into a lighter, more compact, and truly portable test set for field use.
Intrinsic Safety by Design: Beyond standard electrical protections, the resonant circuit itself limits the fault current to a safe value (≈1/Q of test current) in case of a breakdown. This inherent protection, combined with controlled arc quenching, safeguards both the test object and the system.
Robust & Reliable: Designed for demanding field conditions, the system supports continuous operation at full-rated load for over 60 minutes, ensuring completion of even the most extended test procedures.
|
Common Configuration:
|
|||||
|
Model
|
Test Object
|
Main Configurations:
|
|||
|
AC power source
|
Exciting Transformer
|
Reactor
|
Capacitive Voltage Divider
|
||
|
SXBP-27/54/108-108
Test Frequency: 20~300Hz |
31500kVA/35KV Power Transformer
|
10KW 1 unit
|
10KW 1 unit
|
27KV/1A
4 Units Frequency: 20-300Hz |
120KV
|
|
35KV circuit breaker, busbar, insulator
|
|||||
|
10KV(300mm2) cable 2000m
|
|||||
|
35KV(300mm2) cable 500m
|
|||||
|
SXBP-54/108/216-216
Test Frequency: 20~300Hz |
110KV Circuit breaker and busbar
|
15KW 1 unit
|
15KW 1 unit
|
65KV/2A
4 Units Frequency: 20-300Hz |
300KV
|
|
110KV GIS ≤ 10 intervals
|
|||||
|
35KV (300mm2) cable 1500m
|
|||||
|
10KV (300mm2) cable 3000m
|
|||||
|
110KV Full Insulated Transformer
|
|||||
|
SXBP-65/130/260-520
Test Frequency: 20~300Hz |
110KV Circuit Breaker and busbar
|
30KW 1 Unit
|
30KW 1 Unit
|
45KV/1A
6 Units Frequency: 20-300Hz |
200KV
|
|
110KV GIS ≤ 10 intervals
|
|||||
|
110KV (300mm2) cable 800m
|
|||||
|
35KV (300mm2) cable 3000m
|
|||||
|
10KV(300mm2) cable 200m
|
|||||
|
110KV Full Insulated Transformer
|
|||||
|
SXBP-45/90/135/180/270-270
Test Frequency: 20~300Hz |
110KV Insulator, switchgear, GIS and etc.
|
20KW 1 unit
|
20KW 1 unit
|
45KV/1A Six Units
Frequency: 20-300Hz |
200KV
|
|
50MW/110KV Full Insulated Transformer
|
|||||
|
110KV (300mm2) cable 200m
|
|||||
|
35KV Power Transformer, switchgear, CT/PT, cable, and etc.
|
|||||
|
20MW hydrogenerator
|
|||||
|
10KV power transformer, switchgear, CT/PT, cables and etc.
|
|||||
|
SXBP18/36/54
Test Frequency: 20~300Hz |
10KV (300mm2) cable 2000m
|
5KW 1 Unit
|
5KW 1 Unit
|
27KV/1A 2 units or
18KV/1A 3 units Frequency: 20-300Hz |
60KV
|
|
35KV (300mm2) cable 500m
|
|||||
|
10KV power transformer, switchgear, CT/PT and etc.
|