High Frequency Online Rack Mount 6KVA ~ 10KVA Pure Sine Wave Ups Power Without Battery
Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208 VAC.
 When using batteries from 16-19, the unit will de-rate according to the formula: P=Prating x N/20
 If the UPS is installed or used in a place where the altitude is above than 1000m, 
the output must be derated one percent per 100m.
Product specifications are subject to change without further notice.
| Model | ZGD 6K (L) RT | ||||
| PHASE | 1 phase in/ 1 phase out | ||||
| CAPACITY | 6000 VA/6000 W | ||||
| INPUT | |||||
| Nominal Voltage | 208/220/230/240 VAC | ||||
| Voltage Range | 110-300 VAC @ 0~60% load; 140-300 VAC @ 60~80 % load; 176-300 VAC @ 80~100 % load | ||||
| Frequency Range | 46 ~54 Hz or 56~64 Hz | ||||
| Phase | |||||
| Power Factor | ≧ 0.99 @ 100% Load | ||||
| THDi | ≦ 4% @100% load; <6% @ 50% load | ||||
| OUTPUT | |||||
| Output Voltage | 208*/220/230/240 VAC | ||||
| AC Voltage Regulation (Batt. Mode) | ± 1% | ||||
| Frequency Range (Synchronized Range) | 46~54 Hz @ 50 Hz or 56~64 Hz @ 60 Hz | ||||
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | ||||
| Current Crest Ratio | 3:1 (max.) | ||||
| Harmonic Distortion | ≦1.5% THD (Linear Load), ≦ 7 % THD (Non-linear Load) | ||||
| Transfer Time | AC Mode to Batt. Mode | zero | |||
| Inverter to Bypass | zero | ||||
| Waveform (Batt. Mode) | Pure Sinewave | ||||
| Overload | AC Mode | 100%~110%: 10 min; 110%~130%: 1 min; >130%: 1 sec | |||
| Battery Mode | 100%~110%: 30 sec; 110%~130%: 10 sec; >130%: 1 sec | ||||
| BATTERY | |||||
| Standard Model | Battery Type | 12V/7 Ah | |||
| Numbers | 16 | ||||
| Typical Recharge Time | 9 hours recover to 90% capacity | ||||
| Charging Current (Max.) | 1.0A | ||||
| Charging Voltage | 218.4 VDC ±1% | ||||
| Long-run Model | Battery Type | Depending on applications | |||
| Numbers | 16-20** | ||||
| Charging Current (Max.) | 4.0A | ||||
| Charging Voltage | (13.65 VDC x battery number) ± 1% | ||||
| INDICATORS | |||||
| LCD Panel | UPS status, load level, battery level, input/output voltage, discharge timer, and fault conditions | ||||
| PHYSICAL | |||||
| Standard Model | Dimension, DxWxH (mm) | UPS Unit: 600x438x88 [2U]; Battery Pack: 695x438x88[2U] | |||
| Net Weight (kgs) | UPS Unit: 15; Battery Pack: 48 | ||||
| Long-run Model | Dimension, DxWxH (mm) | 600x438x88 [2U] | |||
| Net Weight (kgs) | 15 | ||||
| ENVIRONMENT | |||||
| Humidity | 20-90 % RH @ 0- 40°C (Non-condensing) | ||||
| Noise Level | Less than 55dB@1Meter | ||||
| MANAGEMENT | |||||
| Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | ||||
| Optional SNMP | Power management from SNMP manager and web browser | ||||