DCL compact electric actuators are widely used in HVAC systems, especially for controlling butterfly valves. In modern building automation applications, electric actuators play an essential role in regulating indoor temperature, air conditioning airflow, water circulation, condensate drainage, and hydraulic balancing systems.
In certain installation environments, opening the actuator cover for wiring, commissioning, or maintenance is unavoidable. For applications with high humidity and significant temperature fluctuations between day and night, a thermostatically controlled heater provides effective protection against internal condensation.
To further enhance reliability, DCL actuators feature a patented one-way breathing device that prevents repeated condensation after the heater is switched off. The device allows moisture molecules to escape from the actuator housing while blocking external moisture from entering. This innovative design effectively eliminates condensation-related damage and ensures long-term, stable operation even in harsh environments.
| Type | DCL-05E | DCL-10E | DCL-20E | DCL-40E | DCL-60E | DCL-100E | DCL-200E | DCL-300E |
|---|---|---|---|---|---|---|---|---|
| Power | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC110/220 | AC110/220 | AC110/220 |
| Output Torque | 50Nm | 100Nm | 200Nm | 400Nm | 600Nm | 1000Nm | 2000Nm | 3000Nm |
| Acting Time | 20S | 30S | 30S | 30S | 45S | 30S | 90S | 110S |
| Turning Angle | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° |
| Motor Power | 10W | 25W | 40W | 90W | 90W | 120W | 140W | 140W |
| Rated Current | 1.50/0.24/ 0.16A | 2.12/0.57/ 0.35A | 3.65/0.65/ 0.37A | 6.80/1.12/ 0.57A | 6.80/1.18/ 0.60A | 1.93/0.94A | 1.75/0.96A | 1.75/0.98A |
| Total Weight | 2.5kg | 4.5kg | 9kg | 9.5kg | 10kg | 19kg | 19.5kg | 20kg |
| Input Signal | 4-20mADC,1-5VDC,2-10VDC | |||||||
| Output Singal | 4-20mADC | |||||||
| Basic Error | not more than ±1% | |||||||
| Reciprocating Error | not more than 1% | |||||||
| Dead Space | 0.5%-5.0% adjustable | |||||||
| Damping Characteristic | 0 times | |||||||
| Repeating Error in Actuator | ≤1% | |||||||
| Insulating Resistance | AC24V:100MΩ/250VDC AC110/220V:100MΩ/500VDC | |||||||
| Withstand Voltage Class | AC24V:500VAC 1minute AC110/220V:1500VAC 1minute | |||||||
| Protection Class | IP67 | |||||||
| Installation Angle | 360°at any angle | |||||||
| Electric Interface | Two G1/2 Wate-proof Cable Connectors,one for power line and one for signal line | |||||||
| Ambient Temperature | -20℃~+55℃ | |||||||
| Optional Function | Over-torque protector/Dehumidify Heater/Passive contact switch/Dome indicator/Handle | |||||||
| Remark | Any other input or output signal needed, please specified in purchase order. | |||||||