STM250 modular inverter systems
MAX POWER 6KVA
TBB Power 220Vdc to 220VAC DC to AC inverter Max 6KVA STM250 N+1 module power supply system
STM250 is a sub-rack inverter system integrating TM250 inverter module and TJ20 module. It is
a truly redundant system offering functions of pure sine wave inverter, bypass transfer switch and
monitor into one 19”3U sub-rack. Single module is hot plug design which make the
maintenance an easy job without interruption to your critical load.
Features
|
Model |
TM251 | TM252 | TM252(1600VA) | TM253 |
| Electrical | ||||
| Nominal DC input | 110Vdc,125Vdc , 220Vdc or 240Vdc | |||
| DC operating range | Refer to 2.3 | |||
| Output power | 1Kva | 1.5Kva | 1.6Kva | 2Kva |
| Wave form | Pure sine wave | |||
| Power factor | 0.8 | |||
| Norminal output | 100Vac 110Vac 120Vac 127Vac 208Vac 220Vac 230Vac 240Vac (±2%) | 208Vac 220Vac 230Vac 240Vac (±2%) | ||
| Output frequency | 50/60Hz ± 0.1%Hz | |||
| THD | ≤3% liner load | |||
| ≤5% non-liner load | ||||
| Crest factor | 3:1 | |||
| Efficiency | Low output(100Vac/110Vac/ 120Vac/127Vac):Max 87% High output(208Vac/220Vac/230Vac/ 240Vac):Max 89% | |||
| Overload | 110Vdc,125Vdc,220Vdc and 240Vdc:125-150% 1mins | |||
| 110Vdc,125Vdc,220Vdc and 240Vdc:105-125% 10mins | ||||
| Dynamic response time | < 20ms | |||
| Others | ||||
| Operating Temp. | Full load, -10℃ - 40℃ | |||
| Isolation | 2000Vrms | |||
| Safety | EN60950-1 | |||
| Emmission | EN55022 | |||
| Immunity | EN55022 | |||