100kW Hydrogen Stationary Power Plant for Data Center
We have delivered a 100-kilowatt power plant to a Chinese client, utilizing hydrogen stored in metal hydride tanks as a backup power source for the data center.
| System Rated Power ( kW ) | 100kW |
| Output Voltage (V/AC ) | 415VAC |
| Power Plant Efficiency | >39% |
| -30℃ Cold Start-up to Standby (min) | ≤ 15min |
| Standby to Idle Power | ≤30s @≥5℃ |
| Idle Power Output (kW) | ≤20kW |
| Hydrogen Purity | ≥99.97% Dry Hydrogen (CO<0.1ppm) |
| Hydrogen Inlet Pressure (Bar) | 11-13 Bar |
| Coolant | Up to 50% pure ethylene glycol 50 % to 100% (deionized water); |
| Communication Protocol | CAN2.0B/Modbus TCP |
| Operating Relative Humidity | 99% No Condensing |
| Installation Environment | Outdoors -30°C ~ +45°C |