Remote Battery Capacity Verification System with Segmental Monitoring 0.1C Discharge and Intelligent Charging for Power Plants
Capacity verification through discharge testing remains the most widely recognized method for evaluating battery power capacity. However, traditional on-site verification procedures are cumbersome and consume significant human and material resources, leaving current staffing levels insufficient to meet regulatory maintenance requirements. The remote capacity verification system significantly streamlines this process, enabling efficient completion of battery capacity assessment through discharge testing.
Primarily designed to provide AC uninterruptible power supply for various automated systems, signaling devices, communication networks, remote control execution systems, and emergency lighting equipment in critical facilities such as power plants and substations.
| Order Number | Project | Technical Parameter | Remarks |
|---|---|---|---|
| 1 | DC rated voltage | 85%-120% | |
| 2 | Power supply for the battery cell voltage acquisition module | DC1.5-24V±10% | |
| 3 | Measurement range for the voltage of a 2V battery | 1.5--3V | A reliable alarm shall be triggered when exceeding the measurement range; the measurement accuracy is ≤ ±0.2%, and the reading value increases by +1 mV. |
| Measurement range for the voltage of a 12V battery | 8--15V | ||
| 4 | Measurement range for the total current of the battery pack | 0-350.0V | Measurement accuracy: 50-300 V/≤±(0.5% * reading value + 0.1 V) |
| 5 | Measurement range for the total current of the battery pack | -100--+100A | Measurement accuracy ≤ ±(1%, reading ±0.5 A) |
| 6 | Temperature measurement range for the negative electrode column of a single cell | -10-80℃ | Measurement accuracy ≤ ±1°C |
| 7 | Internal resistance measurement range for a single cell (2 V) | 40~3000mW | Measurement accuracy ≤ (2.5%, reading +15)±mW |
| Internal resistance measurement range for individual cells (1-2 V) | 1500~15000mW | Measurement accuracy ≤ (2.5%, reading +90). Repetition accuracy of internal resistance: 2%.mW | |
| 8 | Measurement range and accuracy of the battery connection resistance | 5~1000mW | Measurement accuracy ≤ (2.5%, reading 5)±±mW |
| 9 | Measurement cycle for the internal resistance of individual cells and the connection resistance of batteries | 1 day - 12 months | The default cycle is 1 month |
| 10 | Discharge current current stabilization accuracy | 10-hour nuclear capacity period | The discharge current remains stable at I.10After discharge completion, the current stabilization accuracy shall not be less than 2%. |
| 11 | Load Environment Temperature Sampling Frequency | ≤5s |